SECTION 9 – SERVICE AND TROUBLESHOOTING
FORM QWC3-NM1
ISSUE DATE:11/20/2020
QUANTECH
165
9
PROBLEM
CAUSE
SOLUTION
LACK OF COOLING EFFECT
1. Fouled evaporator surface Low
suction pressure will be observed.
1. Contact the local Quantech Sales
Representative.
2. Improper flow through the
evaporator.
2. Reduce flow to within chiller design
specs. See Limitations in
SECTION
4 - INSTALLATION
.
3. Low refrigerant charge. Low
suction pressure will be observed.
3. Check subcooling and add charge
as needed.
TABLE 26 -
TROUBLESHOOTING (CONT’D)