SECTION 7 – UNIT CONTROLS
FORM QWC3-NM1
ISSUE DATE:11/20/2020
QUANTECH
115
7
STATUS KEY
Unit Status
Pressing the STATUS key will enable the operator to
determine current chiller operating status. The messag-
es displayed will include running status, cooling de-
mand, fault status, external cycling device status. The
display will be a single message relating to the highest
priority message as determined by the microprocessor.
Status messages fall into the categories of General Sta-
tus and Fault Status.
The following General, Safety, and Warning messages
are displayed when the STATUS key is pressed. Fol-
lowing each displayed message is an explanation per-
taining to that particular message.
General Status Messages
In the case of messages which apply to individual
systems, SYS 1 and SYS 2 messages will both be dis-
played and may be different. In the case of single sys-
tem units, all SYS 2 messages will be blank.
U N I T S W I T C H O F F
S H
U T D
O
W
N
This message informs the operator that the UNIT switch
on the control panel is in the OFF position which will
not allow the unit to run.
R E M O T E C O N T R O L L E D
S H
U T D
O
W
N
The REMOTE CONTROLLED SHUTDOWN mes-
sage indicates that either the BAS system or RCC has
turned the unit OFF, not allowing it to run.
D A I L Y S C H E D U L E
S H
U T D
O
W
N
The DAILY SCHEDULE SHUTDOWN message in-
dicates that the daily/holiday schedule programmed is
keeping the unit from running.
REMOTE STOP
NO RUN PERM
REMOTE STOP NO RUN PERM shows that the re-
mote start/stop contact is open. These contacts are con-
nected to J13-5. A 3-second delay is built into the soft-
ware to prevent nuisance shutdowns due to erroneous
signals on the run permissive input.
S Y S 1 S Y S S W I T C H O F F
S Y S 2 S Y S S W I T C H O F F
SYS SWITCH OFF tells that the system switch under
OPTIONS is turned OFF. The system will not be al-
lowed to run until the switch is turned back ON.
Summary of Contents for QWC3050T-200T
Page 4: ...FORM QWC3 NM1 ISSUE DATE 11 20 2020 QUANTECH 4 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 10: ...FORM QWC3 NM1 ISSUE DATE 11 20 2020 QUANTECH 10 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 28: ...FORM QWC3 NM1 ISSUE DATE 11 20 2020 QUANTECH 28 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 144: ...FORM QWC3 NM1 ISSUE DATE 11 20 2020 QUANTECH 144 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 152: ...FORM QWC3 NM1 ISSUE DATE 11 20 2020 QUANTECH 152 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 166: ...FORM QWC3 NM1 ISSUE DATE 11 20 2020 QUANTECH 166 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 185: ...FORM QWC3 NM1 ISSUE DATE 11 20 2020 QUANTECH 185 NOTES...