QUANTECH
60
Form QCC2-NM1
Issue Date: 5/20/2021
SECTION 5 – TECHNICAL DATA
QCC2040C-QCC2070C Low sound
QCC2040C-070C Ultra low sound
Figure 16 -
Control Wiring Diagram, Details, Dual Circuit
035-20880-103 REV C
NOTES:
I. Field wiring to be in accordance with the current edition of the National Electrical Code as well as all other applicable codes and speci-
fications.
2. Contacts must be suitable for switching 24 VDC, (gold contacts recommended). Wiring must not be run in the same conduit with any
line voltage (class 1) wiring.
3. To cycle unit on and off automatically with contact shown, install a cycling device in series with the flow switch.
See note 2 for contact
rating and wiring specifications.
4. To stop unit (emergency stop) with contacts other than those shown, install the stop contact between terminals 5 and 1. If a stop
device is not installed, a jumper must be connected between terminals 5 and 1. Device must have a minimum contact rating of 6 A at
115 VAC.
5. Contacts are rated at 115 V, 100 VA, resistive load only, and must be suppressed at load by user.
6.
See installation, operation and maintenance manual when optional equipment is used.
7. Optional current readout. 5 V = 200 A.
8. 1MP through 6MP are contained in their respective compressor junction boxes.
Summary of Contents for QCC2015CEE
Page 12: ...QUANTECH 12 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 38: ...QUANTECH 38 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 102: ...QUANTECH 102 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 152: ...QUANTECH 152 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 171: ...QUANTECH 171 Form QCC2 NM1 Issue Date 5 20 2021 Notes...