QUANTECH
157
SECTION 10 – MAINTENANCE
Form QCC2-NM1
Issue Date: 5/20/2021
10
BACnet and Modbus Communications
Chiller data that can be read and modified using spe-
cific BACnet or Modbus Register Addresses; and the
data associated with the addresses, is outlined in the
following description:
ANALOG WRITE POINTS
This data can be read and modified using a BACnet
or Modbus network connection. The Modbus Register
Address for these points is 1025 + AV #.
BINARY WRITE POINTS
This data can be read and modified using a BACnet
or Modbus network connection. The Modbus Register
Address for these points is 1537 + BV #.
ANALOG READ ONLY POINTS
This data can be read using a BACnet or Modbus net-
work connection and can NOT be modified using this
connection. The Modbus Register Address for these
points is 513 + AI #.
BINARY MONITOR ONLY POINTS
This data can be read using a BACnet or Modbus net-
work connection and can NOT be modified using this
connection. The Modbus Register Address for these
points is 1281 + BI #.
Refer to Table 33 for complete list of BACnet and Mod-
bus registers.
The latest data map information is listed
on the Quantech Equipment Integration
website.
Communications Data Map notes
1.
IPU II based units are configured for Native BAC
-
net MS/TP and Modbus RTU communications.
Microgateway or E-Link not required for these
two communication protocols.
2.
BACnet Object Types: 0= Analog In, 1 =
Analog Out, 2= Analog Value, 3= Bina-
ry In, 4 = Binary Output, 5= Binary Value,
8= Device, 15 = Alarm Notification (0 through
127 are reserved ASHRAE Objects).
3. WC= Inches of water column; CFM = Cubic Feet
per Minute; FPM = Feet per Minute: PSI = Lbs
per square inch; Pa = Pascals; kPa = Kilopascals;
PPM = Part per Million; kJ/kg = Kilojoules per
Kilogram.
4.
Water Cooled Scroll units use the same firmware
as Air Cooled Scroll units, ignoring Fan Control.
Summary of Contents for QCC2015CEE
Page 12: ...QUANTECH 12 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 38: ...QUANTECH 38 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 102: ...QUANTECH 102 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 152: ...QUANTECH 152 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 171: ...QUANTECH 171 Form QCC2 NM1 Issue Date 5 20 2021 Notes...