QUANTECH
138
Form QCC2-NM1
Issue Date: 5/20/2021
SECTION 8 – UNIT OPERATION
Condenser fan control - QCC2015C – QCC2070C
Table 20 -
QCC2015C – QCC2070C Low Ambient Condenser Fan Control –
Discharge Pressure Control
FAN
STAGE
ON
OFF
CONTACTOR
I/O BOARD
OUTPUT
FAN #
SYS 1 SYS 2 SYS 1
SYS 2
SYS 1 SYS 2
1
1 FAN
REV
DP > Fan Ctrl On
Press
DP < Fan Ctrl On Press
– Diff. Press.
7M
10M
TB7-8
TB10-8
1 REV 2 REV
2
1 FAN
FWD
DP > Fan Ctrl On
Press
+ 20 psig
(1.38 Bars)
DP < Fan Ctrl On Press.) –
[Diff Press. + 20 psig
(1.38 Bars)]
8M
11M
TB7-9
TB10-9
3
FWD
4
FWD
3
2 FANS
FWD
DP > Fan Ctrl On
Press
+ 40 psig
(2.76 Bars)
DP < Fan Ctrl On Press.) –
[Diff Press. + 40 psig
(2.76 Bars)]
8M & 9M 11M &
12M
TB7-9
&
TB7-10
TB10-9
& TB10-10
1 & 3
FWD
2 & 4
FWD
Table 21 -
QCC2015C – QCC2030C Low Ambient Condenser Fan Control –
Discharge Pressure Control
FAN STAGE
ON
OFF
CONTACTOR
I/O BOARD
OUTPUT
FAN #
Stage 1
"OAT > 25° F or
DP > ctrl_press"
"OAT < 20° F and
DP < ctrl_press - diff_press"
7M
TB7-8
1 REV
Stage 2
"OAT > 45° F or
DP > ctrl 20
psig"
"OAT < 40° F and
DP < ctrl_press - diff 20
psig"
8M
TB7-9
3 FWD
When Low Ambient Control of the fans is
selected, fan control will be by discharge
pressure only.
Summary of Contents for QCC2015CEE
Page 12: ...QUANTECH 12 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 38: ...QUANTECH 38 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 102: ...QUANTECH 102 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 152: ...QUANTECH 152 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 171: ...QUANTECH 171 Form QCC2 NM1 Issue Date 5 20 2021 Notes...