QUANTECH
114
Form QCC2-NM1
Issue Date: 5/20/2021
SECTION 7 – UNIT CONTROLS
Table 11 -
Operation Data
* Block of information repeats for each system
Oper Data Key
** Discharge Air Temperature
Ambient Air Temperature
System 1 Discharge & Suction Pressure
System 2 Discharge & Suction Pressure
*System X Accumulated Hours
*System X Accumulated Starts
Load and Unload Timers
Temp Rate & Temp Error
(Leaving Chilled Liquid Control Only)
Lead System Indicator
Evaporator Pump Contacts
Active Remote Control
Current Feedback One Per Unit
*System X Compressors Status
*System X Run Time
Sys X LLSV & HGSV Status
*System X Condenser Fan Stage
Current Feedback One Per System
** Only displayed when Control Mode is programmed for Discharge
Air Temperature Control.
Oper Data quick reference list
The following table is a quick reference list for infor-
mation available under the OPER DATA key.
LD13347
Print key
The PRINT key allows the operator to obtain a printout
of real-time system operating data or a history printout
of system data at the “instant of the fault” on the last six
faults which occurred on the unit. An optional printer is
required for the printout.
Operating data printout
Pressing the PRINT key and then OPER DATA key al-
lows the operator to obtain a printout of current system
operating parameters. When the OPER DATA key is
pressed, a snapshot will be taken of system operating
conditions and panel programming selections. This
data will be temporarily stored in memory and trans-
mission of this data will begin to the printer. A sample
Operating Data printout is shown below. (Note: Not all
values are printed for all models.)
MILLENNIUM CONDNESING UNIT
UNIT STATUS
2:04PM 01 JULY 09
SYS 1
NO COOLING LOAD
SYS 2
COMPRESSORS RUNNING 2
OPTIONS
AMBIENT CONTROL
STANDARD
LOCAL/REMOTE MODE
REMOTE
CONTROL MODE
LEAVING LIQUID
LEAD/LAG CONTROL
AUTOMATIC
FAN CONTROL
AMB & DSCH PRESS
CURRENT FEEDBACK
NONE
SOFT START
ENABLED
EXPANSION VALVE THERMOSTATIC
PROGRAM VALUES
DSCH PRESS CUTOUT
395 psig
SUCT PRESS CUTOUT
44 psig
LOW AMBIENT CUTOUT 25.0 DEGF
ANTI RECYCLE TIME
600 SECS
FAN CONTROL ON PRESS
240 psig
FAN DIFF OFF PRESS
80 psig
NUMBER OF COMPRESSORS
6
NUMBER OF FANS PER SYSTEM 4
UNIT TRIP VOLTS 3.0
REFRIGERANT TYPE
R-410A
REMOTE UNIT ID PROGRAMMED
1
UNIT DATA
DISCHARGE AIR TEMP 67.0 DEGF
COOLING RANGE 65.0 +/- 5.0 DEGF
AMBIENT AIR TEMP
74.8 DEGF
LEAD SYSTEM
SYS 2
EVAPORATOR PUMP
ON
EVAPORATOR HEATER
OFF
ACTIVE REMOTE CONTROL
NONE
UNIT XXX.X AMPS
X.X VOLTS
SOFTWARE VERSION
C.M08.14.02
Summary of Contents for QCC2015CEE
Page 12: ...QUANTECH 12 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 38: ...QUANTECH 38 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 102: ...QUANTECH 102 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 152: ...QUANTECH 152 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 171: ...QUANTECH 171 Form QCC2 NM1 Issue Date 5 20 2021 Notes...