background image

August 3, 2018   

 

 

      

             7050-145L 

 

 

 

         

                  13

SANTA FE FREESTANDING

Vent Information

A. Venting Termination Minimum Requirements

J or K

X

V

M

I

H

A

V

G

B

V

V

A

B

V

F V

C

B

B

E

L

V

D

V

Electrical

Service

V

N

V

N

V

N

N

V

Inside Corner

FIXED 

CLOSED

OPEN

OPEN

FIXED 

CLOSED

V

X

G

G

Termination Cap

Air Supply Inlet

Gas Meter

Restricted Area

O

P

Figure 13.1

A

12 in.

Above Finish Grade (the grade surface 

must be a non-combustible material

B

12 in.

48 in. no OAK

Open door or window: below or to the side

B

12 in.

Open door or window: above

C

6 in.

Permanently closed window: above, below 

or to the side

D

18 in.

36 in. no OAK

Vertical clearance to a ventilated soffit 

located above the terminal within a hori-

zontal distance of 2 ft from the center-line 

of the terminal 

E

12 in.

Clearance to unventilated soffit

F

12 in.

Clearance to outside corner

G

12 in.

Clearance to inside corner

H

36 in.

Above gas meter/regulator measured from 

horizontal center-line of regulator

I

36 in. USA

72 in. Canada

Clearance to service regulator vent outlet

J

12 in.

48 in. no OAK

Clearance to non-mechanical air supply 

inlet to the building or the combustions air 

inlet to any other appliance

K

10 ft horizontal

3 ft vertical

Clearance to mechanical air supply

L

7 ft.

Above paved sidewalk, paved driveway 

located on 

public

 property

M

12 in.

Under an open veranda, porch, deck or 

balcony

N

See Note 

below*

Electric service: above, below or to the 

side (location must not obstruct or interfere 

with access)

O

24 in.

Adjacent building, fences and protruding 

parts of the structure

P

12 in.

Clearance above roof line for vertical 

terminations

All minimum clearances are listed with an Outside Air Kit (OAK) installed, unless otherwise noted in table below.

24 in.

Above grass, top of plants, wood or any other com-

bustible

12 in.

36 in. no OAK

Clearance from any forced air intake of other appli-

ance

12 in.

Clearance horizontally from combustible wall

15 in.

Vented directly through a wall, minimum length of 

horizontal pipe

6 in. horizontal

12 in. vertical

Minimum horizontal or vertical terminations must 

protrude from wall

*NOTE: 

 Consult local building, fire officials or authorities 

having jurisdiction. Local codes or regulations may 

require different clearances.

NOTICE: 

Do NOT Terminate Vent:

• 

In any location that will allow flue gases or soot from 

entering  or staining the building

•  In any location which could create a nuisance or 

hazard

•  In any enclosed or semi-enclosed area such as a 

carport, garage, attic, crawl space, under a sun deck or 

porch, narrow walkway 

•  Closely fenced area, or any location that can build up 

a concentration of fumes such as a stairwell, covered 

breezeway, etc.

NOTICE:

 Termination must exhaust above air inlet elevation.  

•  It is recommended that at least 60 inches (1.52m) of 

vertical pipe be installed when appliance is vented 

directly through a wall.  This will create a natural draft, 

which will help prevent the possibility of smoke or odor 

venting into the home during a power outage. 

•  It will also keep exhaust from causing a nuisance 

or hazard by exposing people or shrubs to high 

temperatures.  

•  The safest and preferred venting method is to extend 

the vent vertically through the roof or above the roof.

Summary of Contents for SANTAFE-MBK

Page 1: ...llation and service of this appliance should be performed by qualified personnel Hearth Home Technologies recommends HHT Factory Trained or NFI certified professionals WARNING If the information in th...

Page 2: ...Wall Control Location 6 C Tools And Supplies Needed 6 D Inspect Appliance and Components 6 E Install Checklist 7 3 Dimensions and Clearances 8 A Appliance Dimensions 8 B Clearances to Combustibles UL...

Page 3: ...st federal regulations to operate this pellet appliance in a manner inconsistent with operating instructions in this manual EPA Certification 940 14 EPA Certified Emissions 1 8 grams per hour LHV Test...

Page 4: ...om size out air must be installed G California Prop65 WARNING This product and the fuels used to operate this product wood and the products of combustion of such fuels can expose you to chemicals incl...

Page 5: ...the installation Location of the appliance and chimney will affect performance Consideration must be given to Safety convenience traffic flow Placement of the chimney and chimney connector and to mini...

Page 6: ...arefully during the installation to ensure maximum safety and benefit Follow pipe manufacturer instructions for installation and air clearance requirements Reciprocating Saw Channel Locks Hammer Phill...

Page 7: ...appliance and given to the party responsible for use and operation Hearth Home Technologies recommends the following Photographing the installation and copying this checklist for your file That this...

Page 8: ...m 14 5 8 371mm 28 3 4 730mm 9 7 8 251mm 12 3 4 324mm 3 3 4 95mm 6 7 8 175mm 2 1 2 64mm Figure 8 3 Top View with Top Vent Adapter TPVNT 2 and Offset Adapter 812 3570 Figure 8 2 Top View with Top Vent A...

Page 9: ...fset Adapter 812 3570 18 1 4 464mm 21 533mm 16 3 4 427mm 28 3 4 730mm 26 7 8 653mm Figure 9 2 Side View with Top Vent Adapter TPVNT 2 and Offset Adapter 811 0720 Figure 9 4 Side View with Top Vent Ada...

Page 10: ...ance Corner 2 51 H Side Wall to Flue Pipe 3 76 Installations with TPVNT 2 Top Vent Adapter w Heat Shield Clean out TPVNT 6 Top Vent Adapter with Clean out 812 3570 3 to 6 Offset Adapter 811 0720 3 to...

Page 11: ...ded area to the wall thimble 152MM FUEL DOOR OPENING USA INSTALLATIONS A non combustible floor protection is recommended extending beneath the flue pipe when installed with horizontal venting or under...

Page 12: ...Inches Millimeters Inches Millimeters A Height 43 1092 n a n a B Width 38 965 n a n a C Depth 36 914 36 914 D To Side Wall 6 152 n a n a Figure 12 2 NOTE Illustrations reflect typical installations a...

Page 13: ...ces and protruding parts of the structure P 12 in Clearance above roof line for vertical terminations All minimum clearances are listed with an Outside Air Kit OAK installed unless otherwise noted in...

Page 14: ...demands for your house Vent Configurations When installing a pellet appliance with a horizontal vent configuration the frequency of power outages should be considered Power outages during operation wi...

Page 15: ...A CHIMNEY FLUE SERVING ANOTHER APPLIANCE To minimize the effects of negative air pressure Install the outside air kit with the intake facing prevailing winds during the heating season Ensure adequate...

Page 16: ...s not intended to represent any specific fuel type Figure 16 2 3 in or 4 in 76mm or 102mm Diameter Pipe Equivalent Pipe Length In Feet ALTITUDE IN THOUSANDS OF FEET 0 20 30 1 2 3 4 5 6 7 8 9 10 4 in 1...

Page 17: ...installations Must use 3 or 4 inch 76 102mm L or PL Listed pellet venting or Listed double wall pipe and a Quadra Fire Outside Air Kit in mobile homes NOTE In Canada where passage through a wall or p...

Page 18: ...3 in 76mm Minimum Cleanout Cover 12 in 305mm Minimum Ceiling Support 6 in 152mm Flue Connector 6 in 152mm Class A Chimney Connector Adapter 3 in to 6 in 76 152mm Top Vent Kit All three installations a...

Page 19: ...ce Concrete Cap 1 in 25mm Clearance with Firestop 6 in 152mm Minimum Non combustible Hearth Pad Airtight Clean out Door Sheathing 2 in 51mm Minimum Flashing 1 in 25mm Clearance 1 in 25mm Clearance wit...

Page 20: ...tion on wall Use saw to cut opening in wall Cut a 2 1 2 to 3 inch 64 76mm opening on inside wall and a 3 to 3 1 2 inch 76 89mm opening on outside of house 2 Remove cover plate and then install the col...

Page 21: ...he assembly is vertical Figure 21 2 4 Install the 4 mounting screws 5 Drill 2 holes with 26 drill bit through the rear exhaust outlet using the 2 holes already in the short horizontal pipe in the top...

Page 22: ...nder or in front of appliance CAUTION Figure 22 1 Figure 22 2 Figure 23 3 1 Separate the body of the thermostat from the mounting plate by gently pulling the two pieces apart Figure 22 1 2 Use a drill...

Page 23: ...firebox 4 Push the logs to the far left and far right against the sides of the firebox Figure 23 2 5 To clean the logs use a vacuum and a soft brush attachment or a paint brush Figure 23 2 Figure 23 1...

Page 24: ...24 Part Number 811 0872 Spark Arestor Cap Roof Flashing Storm Collar Joist Shield Firestop Double Wall Connector Pipe Figure 24 1 CAUTION Never draw outside combustion air from Wall floor or ceiling...

Page 25: ...August 3 2018 7050 145L 25 SANTA FE FREESTANDING 8 Reference Materials A Service and Maintenance Log Date of Service Performed By Description of Service...

Page 26: ...26 7050 145L August 3 2018 SANTA FE FREESTANDING Date of Service Performed By Description of Service...

Page 27: ...utside Air Kit 412 7100 Pull Rod Handle PULLROD HNDL Smart Batt Il Battery Operated 841 0970 Smart Stat Il receiver Requires 110 VAC 841 0960 Thermostat Programmable PROG STAT Top Vent Adapter TPVNT 2...

Page 28: ...purchased installed _________________________________________________________________________ Serial Number ____________________________________ Location on appliance ___________________________ Deal...

Reviews: