Page 28
December 1, 2011
Santa Fe NZ Pellet Stove
R
7068-114B
7
Flueing Information
A. Chimney and Exhaust Connection
The flue must be installed by a suitably qualified person in
accordance with AS/NZS2918:2001 and the manufactures
instructions. The SANTAFE pellet fire range use a fan
powered exhaust system with a slightly negative pressure
in the combustion chamber and a slightly positive pressure
in the flue.
Flue parts need to be
1. Combustion and condensation proof (stainless
steel)
2. Have no restrictions or draft adjustment de
-
vices
3. Must be suitably insulated where they are
outside the room the fire is located
4. Have the correct clearances from combustible
materials
5. Free standing models must have a T adapter
/cleanout at the connection to the fire.
6.
INSTALL FLUE AT CLEARANCES SPECIFIED BY THE
FLUE MANUFACTURER.
7. Secure flue system to the appliance with
at least three (3) screws/rivets per the pipe
manufacturer’s instructions. Also secure all
connector pipe joints with at least three (3)
screws/rivets through each joint.
8. DO NOT INSTALL A FLUE DAMPER IN THE
EXHAUST VENTING SYSTEM OF THIS
UNIT.
9. DO NOT CONNECT THIS UNIT TO A CHIM
-
NEY FLUE SERVING ANOTHER APPLI
-
ANCE.
Switch recommends the use of Davin flu kits as outlined on
page 29 and page 30. These have been tested and
approved for use with the SANTAFE range of fires if you
intend to use a different flue kit you will need to consult with
your local council
NOTE: Seal pipe joints with high temperature silicone , or
equivalent, (250°C minimum rated only). Do not put sealant
inside of pipe.
Vent surfaces get HOT, can cause burns if
touched. Non-combustible shielding or guards
may be required.
WARNING
NOTE:
• Illustrations reflect typical installations and are
FOR DESIGN PURPOSES ONLY.
•
Illustrations/diagrams are not drawn to scale.
•
Actual installation may vary due to individual
design preference.
B. Outside Air Kit Instructions
There are two Outside Air Kits that will work with this
appliance. One kit, 811-0872 uses a 2 inch flex hose
(included) and uses hose clamps to secure the hose. The
other kit, OAK-3, uses a 3 inch flex hose (not included) and
uses wire ties to secure the hose.
Parts Included in 2 inch Kit 811-0872:
1 piece of 2
inch x 3 ft. flex hose, 2 hose clamps, 1 collar assembly, 1
termination cap assembly, trim ring, 1 intake air channel,
fasteners (Discard the air intake channel, it is not needed for
this appliance.
Parts Included in 3 inch Kit OAK-3:
2 wire ties, 1
collar assembly, 1 termination cap assembly, 1 trim ring,
fasteners.
Tools Needed:
Phillips Head screw driver; wire cutters;
hole saw or jig saw, and the length of flex hose needed for
your installation if using the 3 inch kit.
10. Measure distance from floor to air vent opening in ap
-
pliance and mark location on wall.
11. Use saw to cut opening in wall.
•
2 inch kit:
Cut a 2-1/2 to 3 inch opening on inside
wall and a 3 to 3-1/2 inch opening on outside of
house.
•
3 inch kit:
Cut a 3-1/2 to 4 inch opening on inside
wall and a 4 to 4-1/2 inch opening on outside of
house.
12. Use wire tie or hose clamp depending on the Outside
Air Kit to secure flex pipe to collar assembly.
13. Slide trim ring over flex pipe and run pipe through wall.
14. Attach flex pipe to outside termination cap with second
wire tie or hose clamp.
15. Secure termination cap to outside surface.
16. Secure trim ring to interior wall.
WARNING
Maintain minimum clearances to combustibles
Fire Risk.
Follow Flue Manufacturer’s Instructions for
Proper Installation