Grand Bay 40 Direct Vent Freestanding
Page 12
January 2000
THERMOSTAT INSTALLATION
OPTIONAL THERMOSTATS
Manual Thermostat
Part #812-2880
Anticipator Setting 1.2
Electronic Setback
Part #811-0520
RECOMMENDED MAXIMUM LEAD
LENGTH (TWO WIRE) WHEN USING
WALL THERMOSTAT/SWITCH
Wire Size
Maximum Length
16 gauge
65 feet
18 gauge
40 feet
20 gauge
25 feet
22 gauge
18 feet
If desired, a thermostat may be installed to regulate the Quadra-Fire GBDV-40. It is important to
use a thermostat designed for millivolt operation. Do not connect this stove to a thermostat serving
any other appliance.
Connect the thermostat wires to the two center screw terminals in the thermostat connection block,
located at the lower rear of the unit. Turn off the manual switch, located on the control panel.
REMOTE CONTROL
A remote control or a wall switch may be wired to the thermostat terminals. Contact your Quadra-
Fire dealer or service person for details (see page 39 for part number).
BLOWER POWER CORD
The blower cord is located at the rear of the stove, and needs to be routed to a three-prong outlet
with correct polarity. Be sure that the stove is electrically grounded in accordance with local codes,
with a current version of CSA C22 (in Canada), or in the absence of local codes, with the National
Electric Code ANSI/NFPA 70-1987.
WARNING
Do not cut the grounding terminal off under any circumstances.
Do not route the power cord under the body of the stove due to high temperatures.