Page
22
AN-X4-ABRIO-HMI
Feb 2023
Status File Information
AN-X maps remote I/O diagnostic counters, rack status and block transfer status to a PLC-5 status
file. An HMI can access the data by reading the status file.
The following tables show the contents.
Diagnostic Counters
Counter
Status file
Description
TX FRAMES
S2:0
Transmitted packets
RX FRAMES
S2:1
Good received packets
CRC ERRORS
S2:2
CRC errors
ABORT ERRORS
S2:3
Abort errors
NOISE ERRORS
S2:4
Noise errors
TIMEOUTS
S2:5
Timeouts, packet sent, no reply
PROTOCOL ERRORS
S2:6
Protocol errors
PROTOCOL MASK
S2:7
Indicates cause of protocol error
UpdCur
S2:8
Update time for the last scan, in ms
UpdAvg
S2:9
Average time of the last 32 scans, in ms
UpdMin
S2:10
Minimum scan time, in ms, since the last reset
UpdMax
S2:11
Maximum scan time, in ms, since the last reset
S2:12-S2:15
Reserved
The minimum update time is set to 65535 on reset.
The maximum update time is set to 0 on reset.
Rack status
Status table element
Contents
S2:16
Output Status racks 00-03
S2:17
Output Status racks 04-07
S2:18
Output Status racks 10-13
S2:19
Output Status racks 14-17
S2:20
Output Status racks 20-23
S2:21
Output Status racks 24-27
S2:22
Output Status racks 30-33
S2:23
Output Status racks 34-37
S2:24
Output Status racks 40-43
S2:25
Output Status racks 44-47
S2:26
Output Status racks 50-53
S2:27
Output Status racks 54-57