INSTALLATION
Q6S/Q6M
© 2020 Q-Tran Inc. All rights reserved | 155 Hill St. Milford, CT 06460 | 203-367-8777 | [email protected] | www.q-tran.com
Specification subject to change. Rev-09-29-20
Rough In Wiring
Example:
25A max per NEC 411: use #10 AWG min
For 20A, use #12 AWG min
For 15A use #14 AWG min
Please note amperage may increase with higher taps.
L.V. = Class 1 wiring per NEC - wire must be sized to be
equal to or greater than shown.
When the voltage goes down by a factor of 10 (120V to 12V) the
amperage goes up by a factor of 10 (2.5A to 25A)
Primary
Secondary
Secondary
Circuit Breaker
5A
10A
15A
20A
25A
L.V.
Gauge
14 AWG
14 AWG
14 AWG
12 AWG
10 AWG
Max Load
12V
60W
120W
180W
240W
300W
Max Load
24V
120W
240W
360W
480W
600W
12V
25A
120V
2.5A
Transformer
300VA
#10 AWG min
= 2.5A
= 25A
300VA
120V
300VA
12V
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
NOTE: Switch or dimmer are always on the primary
15A circuit breaker
use #14 AWG
minimum
20A circuit breaker
use #12 AWG
minimum
The neutral must be clean.
Run a “virgin” neutral for each PSC.
Low Voltage Runs = High Amps
Secondary Breaker Amperage
Keep Runs Short! Get The Tap Right!
Get The Wire Gauge Right
Both primary and secondary wiring to be Class 1 per
NEC unless Class 2 option is ordered
Download our Voltage Drop Calculator at:
www.Q-Tran.com
120V Primary
12V Secondary
2.5A Primary
114V when dimmer
is @ full bright
25A max
per L.V. load
300VA
300VA
120V switch