INSTALLATION

         

Q6S/Q6M

© 2020 Q-Tran Inc. All rights reserved | 155 Hill St. Milford, CT 06460 | 203-367-8777 | [email protected] | www.q-tran.com 

Specification subject to change. Rev-09-29-20

Mounting Options

MOUNT

 unit in any of the following configurations: 

Do not recess. If you need a recessed unit, you need to order our QT series.

VOLTAGE DROP

• 

To minimize voltage drop the proper gauge wire must be pulled between     

the Q-Tran power supply and the load.

• 

Q-Tran offers a free voltage drop calculator on our website  

(www.q-tran.com) or you can download our free voltage drop app for 

iPhone, iPad or android devices (click link on our site).

• 

Below is a quick reference chart of minimum acceptable wire gauges.

(Q-Tran urges each installer to view our full calculator.)

BEFORE INSTALLING DOOR 

Please make sure the output voltage at the lamps is between 11.4–12 volts 

for a 12V system or 22.8–24 volts for a 24V system. Check this voltage with 

a true RMS volt meter & take voltage reading at the lamps.

CONNECT SECONDARY

(For detailed look at secondary, see Diagram B)

Connect low voltage fixtures in one of the following methods:

CONNECT PRIMARY

(For detailed look of primary, see Diagram A)

NOTE: 

Voltages are fixed and can only be changed at the 

factory. Voltages come in 120V, 230V or 277V.

1

3

5

4

2

Rod Suspension

Surface Wall

Surface Ceiling

Surface Floor

NOTE: Rods not included.

120V input

Switch

120V input

Dimmer

114V output

120V output

NEU

GND

HOT

GND
NEU

12V

NEU

GND

11V
12V
13V

11V
12V
13V

GND
NEU

{

HOT

{

GND

OR

24V

26V

TAP 1

TAP 2

13V

Secondary

Circuit Breaker

2.5A

4 A
5 A

14 AWG
14 AWG
14 AWG

-

60W

120W

60W

100W
120W

 L.V.

Gauge

Max Load 

12V 

Max Load 

24V

Secondary Breaker Amperage

*

* L.V. = wiring per NEC - wire must be sized to be equal to or greater than shown. 

#14

12V

#14 TYP.

#14

#14

#12

#12

#10

#10

#10

#10

#14

#14

#12

#12

#12

#14

25A #10

25A #10

100W

100W

12V

12V

12V

A.

B.

C.

D.

24V

Equal Gauge - Equal Length

Equal Gauge - Equal Length

Vary Wire Gauge to Keep Voltage Equal

Vary Wire Gauge to Keep Voltage Equal

200W

Transformer

15’

15’

35’

35’

15’

15’

15’

15’

Diagram A.

Diagram B.

Diagram C.

Diagram D.

DO NOT USE THIS METHOD TO WIRE YOUR LOW-VOLTAGE FIXTURES!

Summary of Contents for Q6S

Page 1: ...Prim V Sec V No Brk Amp2 Choke Color3 50DT 100DT 150DT 300DT 120 60Hz 277 60Hz 12V 24V 1 2 3 5 10 12 5 15 20 25 WH Standard BK 2 Secondary Breaker Amperage Amps Max 12V Load Max 24V Load 5 60W 120W 10 120W 240W 12 5 150W 300W 15 180W 360W 20 240W 480W 25 300W 600W 3 Color WH White Standard BK Black Powder Coat Finish Choke CK S 150W 300W Choke not required from 50W 100W 1 2 3 4 5 6 WALL CEILING FL...

Page 2: ...e connected to one 1 of the primary taps up to the full watt rating of the PSC 20 derating required The advantage is that the PSC can be tapped to recover voltage drop and produce between 85 100 light output NOTE See Voltage Drop Calculator at www q tran com Secondary Circuit Up to three 3 magnetic circuit breaker Amps 5A 10A 12 5A 15A 20A 25A NOTE Breakers are sized to the feed load per N E C Art...

Page 3: ...age reading at the lamps CONNECT SECONDARY For detailed look at secondary see Diagram B Connect low voltage fixtures in one of the following methods CONNECT PRIMARY For detailed look of primary see Diagram A NOTE Voltages are fixed and can only be changed at the factory Voltages come in 120V 230V or 277V 1 3 5 4 2 Rod Suspension Surface Wall Surface Ceiling Surface Floor NOTE Rods not included 120...

Page 4: ... AWG 14 AWG 12 AWG 10 AWG Max Load 12V 60W 120W 180W 240W 300W Max Load 24V 120W 240W 360W 480W 600W 12V 25A 120V 2 5A Transformer 300VA 10 AWG min 2 5A 25A 300VA 120V 300VA 12V ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF NOTE Switch or dimmer are always on the primary 15A circuit breaker use 14 AWG minimum 20A circuit breaker use 12 AWG minimum The neutral must be clean ...

Page 5: ...d A number 6 or 8 gauge wire for instance can not be terminated on most L V products Diagram A For 12V track rail or cable system that is rated for 25A requires a minimum of 10 gauge wire Runs should be approximately the same length Diagram B For LV cove lighting the VDC might show you to vary the wire gauge to equalize the voltage at the lamp Running the same gauge wire to all runs may be wrong D...

Page 6: ...OWN BLUE YELLOW VIOLET Tp Bkr s PRIMARY VOLTAGE SECONDARY 24 VAC Ɣ USE WIRE NUTS OR TERMINAL BLOCKS FOR LOAD CONNECTIONS Ɣ DASHED LINES INDICATE ELECTRICAL CONTRACTOR WIRING L O A D L O A D OR TAP2 120V GREY RED 277V 4 50 Q6 WIRING DIAGRAM 3 50 If a transformer is wired from the factory for 12V for 24V secondary wiring Disconnect the blue and yellow wires from terminal blocks and connect together ...

Page 7: ...our information on the lines provided Manufacturer Model number ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF Risk of Fire Electric Shock Transformer should be installed by a Licensed electrician in accordance with the N E C and all local codes in force Wear rubber shoes and work on a sturdy wooden or fib...

Reviews: