INSTALLATION

         

Q6S/Q6M

© 2020 Q-Tran Inc. All rights reserved | 155 Hill St. Milford, CT 06460 | 203-367-8777 | [email protected] | www.q-tran.com 

Specification subject to change. Rev-09-29-20

Connecting and Configuring

B

E

A

C

B

D

PRIMARY (Input Wires)

SECONDARY (Output Wires)

CHOKE

Standard on all units 

TRANSFORMER 

Small – 50W - 300W

DIVIDER 

A

B

C

D

E

Input voltage is fixed and can only be changed
at the factory. Input voltage is indicated on side
of the housing.

Medium – 500W - 750W
Large – 900W - 1800W

Secondary Circuit Breakers     
Secondary Common     
DO NOT EXCEED TOTAL AMPS OF SECONDARY         
CIRCUIT BREAKERS     
Output voltage is wired as ordered (12V or 24V)     

but can be changed by a licensed electrician.  

CHOKE

GREEN

GND

NEU

HOT

GND

NEU

HOT

GND

WHITE

TAP1

(120V)

BLACK

ORANGE

(277V)

WHITE

BROWN

BLUE

YELLOW

VIOLET

Tp

Bkr(s).

PRIMARY

VOLTAGE 

12V

WIRING DIAGRAM

24V

WIRING DIAGRAM

SECONDARY

12 VAC

Ɣ

  USE WIRE NUTS OR TERMINAL BLOCKS FOR LOAD CONNECTIONS

Ɣ

  DASHED LINES INDICATE ELECTRICAL CONTRACTOR WIRING

L

O

A

D

L

O

A

D

OR

TAP2

(120V)

GREY

RED

(277V)

CHOKE

GREEN

GND

WHITE

TAP1

(120V)

BLACK

ORANGE

(277V)

WHITE

BROWN

BLUE

YELLOW

VIOLET

Tp

Bkr(s).

PRIMARY

VOLTAGE 

SECONDARY

24 VAC

Ɣ

  USE WIRE NUTS OR TERMINAL BLOCKS FOR LOAD CONNECTIONS

Ɣ

  DASHED LINES INDICATE ELECTRICAL CONTRACTOR WIRING

L

O

A

D

L

O

A

D

OR

TAP2

(120V)

GREY

RED

(277V)

4.50" 

Q6 WIRING DIAGRAM 

3.50" 

If a transformer is wired from the factory for 12V, 
for 24V secondary wiring: Disconnect the blue and 
yellow wires from terminal blocks and connect 
together with wire nut. The brown wire now 
becomes the common side of the load, and the 
violet wire should be connected to the secondary 
circuit breaker, which is the line side of the load. 
Please refer to the wiring diagrams on this page.

12 

   

24 

If a transformer is wired from the factory for 
24V, for 12V secondary wiring: Disconnect the 
blue and yellow wires from terminal block. 
Connect yellow and brown wire into terminal 
block, which becomes the common side of the 
load. Connect blue and violet wires into 
terminal block, which should be connected to 
the secondary circuit breaker(s) which 
becomes the line side of the load Please refer 
to the wiring diagrams on this page.

24 

   

12

Auto reset thermal circuit breaker mounted to core of toroid Hydraulic magnetic manual reset circuit breakers

Tp

Terminal block connection
Polarity

Choke or inductor on primary
to reduce inrush current.

Summary of Contents for Q6S

Page 1: ...Prim V Sec V No Brk Amp2 Choke Color3 50DT 100DT 150DT 300DT 120 60Hz 277 60Hz 12V 24V 1 2 3 5 10 12 5 15 20 25 WH Standard BK 2 Secondary Breaker Amperage Amps Max 12V Load Max 24V Load 5 60W 120W 10 120W 240W 12 5 150W 300W 15 180W 360W 20 240W 480W 25 300W 600W 3 Color WH White Standard BK Black Powder Coat Finish Choke CK S 150W 300W Choke not required from 50W 100W 1 2 3 4 5 6 WALL CEILING FL...

Page 2: ...e connected to one 1 of the primary taps up to the full watt rating of the PSC 20 derating required The advantage is that the PSC can be tapped to recover voltage drop and produce between 85 100 light output NOTE See Voltage Drop Calculator at www q tran com Secondary Circuit Up to three 3 magnetic circuit breaker Amps 5A 10A 12 5A 15A 20A 25A NOTE Breakers are sized to the feed load per N E C Art...

Page 3: ...age reading at the lamps CONNECT SECONDARY For detailed look at secondary see Diagram B Connect low voltage fixtures in one of the following methods CONNECT PRIMARY For detailed look of primary see Diagram A NOTE Voltages are fixed and can only be changed at the factory Voltages come in 120V 230V or 277V 1 3 5 4 2 Rod Suspension Surface Wall Surface Ceiling Surface Floor NOTE Rods not included 120...

Page 4: ... AWG 14 AWG 12 AWG 10 AWG Max Load 12V 60W 120W 180W 240W 300W Max Load 24V 120W 240W 360W 480W 600W 12V 25A 120V 2 5A Transformer 300VA 10 AWG min 2 5A 25A 300VA 120V 300VA 12V ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF NOTE Switch or dimmer are always on the primary 15A circuit breaker use 14 AWG minimum 20A circuit breaker use 12 AWG minimum The neutral must be clean ...

Page 5: ...d A number 6 or 8 gauge wire for instance can not be terminated on most L V products Diagram A For 12V track rail or cable system that is rated for 25A requires a minimum of 10 gauge wire Runs should be approximately the same length Diagram B For LV cove lighting the VDC might show you to vary the wire gauge to equalize the voltage at the lamp Running the same gauge wire to all runs may be wrong D...

Page 6: ...OWN BLUE YELLOW VIOLET Tp Bkr s PRIMARY VOLTAGE SECONDARY 24 VAC Ɣ USE WIRE NUTS OR TERMINAL BLOCKS FOR LOAD CONNECTIONS Ɣ DASHED LINES INDICATE ELECTRICAL CONTRACTOR WIRING L O A D L O A D OR TAP2 120V GREY RED 277V 4 50 Q6 WIRING DIAGRAM 3 50 If a transformer is wired from the factory for 12V for 24V secondary wiring Disconnect the blue and yellow wires from terminal blocks and connect together ...

Page 7: ...our information on the lines provided Manufacturer Model number ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF Risk of Fire Electric Shock Transformer should be installed by a Licensed electrician in accordance with the N E C and all local codes in force Wear rubber shoes and work on a sturdy wooden or fib...