background image

INSTALLATION

         

Q6S/Q6M

© 2020 Q-Tran Inc. All rights reserved | 155 Hill St. Milford, CT 06460 | 203-367-8777 | [email protected] | www.q-tran.com 

Specification subject to change. Rev-09-29-20

Rough In Wiring

Equalizing Voltage Drop

When installing multiple fixtures or loads from a single remote PSC, 

it is important to have approimately the same voltage at each lamp. 

Many installations require different length runs to the loads which 

may require different wire gauges to equalize the voltage. It is 

important to have approximately the same voltage at each lamp so 

the light output appears to be the same. Use Q-Tran’s Voltage Drop 

Calculator to easily determine the correct wire gauge.

3 Key Points you must know:

1 - The voltage of the lamp specified

2 - The amperage rating of the product

3 - The maximum wire gauge that can be terminated at the load. A 

number 6 or 8 gauge wire, for instance, can not be terminated on 

most L.V. products.

Diagram A - For 12V track, rail, or cable system that is rated for 

25A requires a minimum of #10 gauge wire. Runs should be 

approximately the same length.

Diagram B - For LV cove lighting, the VDC might show you to vary 

the wire gauge to equalize the voltage at the lamp. Running the 

same gauge wire to all runs may be wrong.

Diagram C - For recessed or mono point fixtures powered from a 

single PSC, it is a recommended that all secondary runs be the 

same length and the same gauge; EQUAL LENGTH - EQUAL 

GAUGE. All surplus wire must not be coiled but made into a long 

loop.

Diagram D - For commerical installations requiring conduit, this 

diagram shows an alternate wiring method. Also applicable to 

residential installations.

Diagram A.

Equal Gauge - Equal Length

Vary Wire Gauge to Keep Voltage Equal

Equal Gauge - Equal Length

Vary Wire Gauge to Keep Voltage Equal

Diagram B.

Diagram C.

Must go back to the PSC as shown in example C or D.

DO NOT USE THIS METHOD!

Diagram D.

Summary of Contents for Q6S

Page 1: ...Prim V Sec V No Brk Amp2 Choke Color3 50DT 100DT 150DT 300DT 120 60Hz 277 60Hz 12V 24V 1 2 3 5 10 12 5 15 20 25 WH Standard BK 2 Secondary Breaker Amperage Amps Max 12V Load Max 24V Load 5 60W 120W 10 120W 240W 12 5 150W 300W 15 180W 360W 20 240W 480W 25 300W 600W 3 Color WH White Standard BK Black Powder Coat Finish Choke CK S 150W 300W Choke not required from 50W 100W 1 2 3 4 5 6 WALL CEILING FL...

Page 2: ...e connected to one 1 of the primary taps up to the full watt rating of the PSC 20 derating required The advantage is that the PSC can be tapped to recover voltage drop and produce between 85 100 light output NOTE See Voltage Drop Calculator at www q tran com Secondary Circuit Up to three 3 magnetic circuit breaker Amps 5A 10A 12 5A 15A 20A 25A NOTE Breakers are sized to the feed load per N E C Art...

Page 3: ...age reading at the lamps CONNECT SECONDARY For detailed look at secondary see Diagram B Connect low voltage fixtures in one of the following methods CONNECT PRIMARY For detailed look of primary see Diagram A NOTE Voltages are fixed and can only be changed at the factory Voltages come in 120V 230V or 277V 1 3 5 4 2 Rod Suspension Surface Wall Surface Ceiling Surface Floor NOTE Rods not included 120...

Page 4: ... AWG 14 AWG 12 AWG 10 AWG Max Load 12V 60W 120W 180W 240W 300W Max Load 24V 120W 240W 360W 480W 600W 12V 25A 120V 2 5A Transformer 300VA 10 AWG min 2 5A 25A 300VA 120V 300VA 12V ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF NOTE Switch or dimmer are always on the primary 15A circuit breaker use 14 AWG minimum 20A circuit breaker use 12 AWG minimum The neutral must be clean ...

Page 5: ...d A number 6 or 8 gauge wire for instance can not be terminated on most L V products Diagram A For 12V track rail or cable system that is rated for 25A requires a minimum of 10 gauge wire Runs should be approximately the same length Diagram B For LV cove lighting the VDC might show you to vary the wire gauge to equalize the voltage at the lamp Running the same gauge wire to all runs may be wrong D...

Page 6: ...OWN BLUE YELLOW VIOLET Tp Bkr s PRIMARY VOLTAGE SECONDARY 24 VAC Ɣ USE WIRE NUTS OR TERMINAL BLOCKS FOR LOAD CONNECTIONS Ɣ DASHED LINES INDICATE ELECTRICAL CONTRACTOR WIRING L O A D L O A D OR TAP2 120V GREY RED 277V 4 50 Q6 WIRING DIAGRAM 3 50 If a transformer is wired from the factory for 12V for 24V secondary wiring Disconnect the blue and yellow wires from terminal blocks and connect together ...

Page 7: ...our information on the lines provided Manufacturer Model number ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF Risk of Fire Electric Shock Transformer should be installed by a Licensed electrician in accordance with the N E C and all local codes in force Wear rubber shoes and work on a sturdy wooden or fib...

Reviews: