Trip Class
Application Description
5
Small fractional horsepower motors where acceleration times are almost
instantaneous or where extremely quick trip times are required.
10
(Fast Trip) Hermetic refrigerant motors, compressors, submersible pumps and
general-purpose motors that reach rated speed in less than 4 seconds.
15
Specialized
applications
20
(Standard Trip) Most NEMA-rated, general-purpose motors will be protected by
this setting.
30
(Slow Trip) Motors with long acceleration times (>10 seconds) or high inertia
loads.
J prefix
Programming any of the trip classes with the J Prefix will enable jam protection.
This additional protection is enabled 1 minute after the motor starts and
provides a 2-second trip time for motors exceeding 400% of the OC setting,
regardless of trip class.
Table 4. Trip Class Descriptions
Figure 4. Overload Trip Curves