Mechanical
Dimensions
3.0"H x 5.1"D x 3.6"W
Terminal Torque
7 in.-lbs.
Enclosure Material
Polycarbonate
Weight
1.2 lbs.
Maximum Conductor Size
0.65" with insulation
Environmental
Temperature Range
Ambient Operating: -40° to 70°C (-40° to 158°F)
Ambient Storage: -40° to 80° C (-40° to 176°F)
Pollution Degree
3
Class of Protection
IP20, NEMA 1
Relative Humidity
10-95%, non-condensing per IEC 68-2-3
Programmable Operating Points
Range
MULT- # of Conductors or CT Ratio (XXX:5)
1–10 Conductors or 100–800 Ratio
HP
.1–50
FLA
0, (20–207A) ÷ MULT
or 0, 80–140% of CT primary (992 max.)
EFF/PF
E00–E99, P00–P99
OC- Overcurrent Threshold
(20–100A) ÷ MULT
or 80–140% of CT Primary (992 max.)
TC- Overcurrent Trip Class *
5, J5, 10, J10, 15, J15, 20, J20, 30, J30
CUB- Current Unbalance Threshold
2–25% or 999%
PWS- Power Setpoint Range
1 = 0.01–0.99 kW
(for LPR and HPR setpoints)
2 = 1.00–9.95 kW
3 = 10.0–99.5 kW
NOTE: LPR can be set to “0” and
4 = 100–650 kW
HPR to “off" to disable these features
5 = 0.01–1.30 hp
6 = 1.34–13.3 hp
7 = 13.4–133 hp
8 = 134–871 hp
LPR- Low Power
Range determined by PWS
HPR- High Power
Range determined by PWS
RD1- Rapid Cycle Timer
0, 2–500 Seconds
RD2- Restart Delay After All Faults Except
Underload (motor cool-down timer)
0, 2–500 Minutes
RD3- Restart Delay After Underload
(low-flow recovery timer)
0, 2–500 Seconds, A (Automatic)
COMM- RS485 Address
A01–A99 or OP1 for 4–20mA output
FS- Full Scale
(required when using 4-20 mA module)
Full Scale Range (determined by PWS)
PWS =1
.4–1.39 kW
2
1.4–14.0 kW
3
14.0–138 kW
4
140–654 kW
5
.53–1.86 hp
6
1.87–18.7 hp
7
18.7–185 hp
8
187–877 hp
NOTES:
SymCom's Power Monitor/Motor Protection Relay can be programmed prior to installation
by applying 120VAC between the L1 and L2 terminals (except 575 Volt model). Power applied must
be 110VAC or greater.
* If a J prefix is displayed in trip class setting, jam protection is enabled.
** on a well-balanced system within recommended current range