P1-35 Local address
1~6 is for FC own
communication address;
0 is not for FC, but for
upper monitoring and
control device (e.g.,
PLC)
1
1
☆
The local address is set
automatically when you set
parameter P1.47
P1-36 Baud rate
0: 4800
1: 9600
2: 19200
3: 38400
1 bPS
1
☆
bPS = Bit per second
P1-37 Data format
0: no parity bit (8.N.1.)
1: odd parity bit (8.O.1.)
2: even parity bit (8.E.1.)
1
0
☆
P1-38 Response delay
0 - 20 (0-200)
1ms
2
☆
P1-43
Speed ratio of main and
auxiliary windings of
single-phase motor
10 - 200
1
100
☆
P1-44
Single-phase motor
current correction factor
50 - 200
1
150
☆
P1-45
Time to reset of water
shortage protection
0 - 9999
1
10
☆
P1-47 Hidden parameter menu
0: Displayed
1: Hidden
1
1
☆
7.5 Parameter setting procedure
For commonly used parameters P0.00 - P0.04, the setting procedure is as follows.
Setting P0.00 (pressure setting
)
-
+
3. 0
P0
P0. 00
3. 0
4. 0
MENU
RUN/
STOP
P0. 01
P0
4. 0
RUN/
STOP
RUN/
STOP
MENU
MENU
Notes: press the "+" or "-" button to change the pressure setting to 4.0 in the displayed stop state.
P0.01 setting (Starting pressure differential)
-
+
4. 0
P0
P0. 00
P0. 01
0. 3
RUN/
STOP
0. 4
P0. 02
P0
4. 0
MENU
RUN/
STOP
RUN/
STOP
MENU
MENU
-
+