P0-05
Pressure calibration
factor
0.750 - 1.250
0.001
1.000
☆
If the FC shows a pressure of 3 bar
but the actual pressure in the system
is 3.6 bar, set this value to 1.2 bar
(3.6÷3=1.2)
P0-06 Proportional gain P1
0,0 - 100,0
0.1
2.00s
☆
P0-07 Integration gain I1
0.00s - 10.00s
0.01s
0.50s
☆
P0-08
Selection of PID idle
mode function
0:
idle mode off
1:
i
dle mode 1
2:
idle mode 2
1
1
☆
Idle mode 1:
The system performs
sleep processing based on pressure,
frequency and time. At this time, the
water leakage coefficient, the
pressure holding detection time and
the sleep frequency are valid.
Idle mode 2:
The system performs
sleep processing based on pressure,
frequency and time. At this time, the
system does not evaluate the water
leakage coefficient.
P0-09
Detection delay PID idle
mode detection
0,0 - 100,0
0.1s
5.0
☆
P0-10
PID trigger detection
delay from idle mode
0,0 - 100,0
0.1s
3.0
☆
P0-11
Low level adjacency
frequency of PID idle
mode detection
20.00 Hz up to the
upper limit frequency
0.01Hz
30.00
☆
PID runs at idle frequency. After time
P0-12 PID goes to idle mode
P0-12
Low level operation time
of PID idle mode
0,0s
– 120,0s
0.1s
5.0
☆
P0-13
PID idle mode deviation
pressure
0.0bar - 1.0bar
0.1bar
0.2
☆
P0-14
Automatic start-up on
power-up
0: off
1: on
1
0
☆
When the parameter is set to "1" -
the system starts automatically after
switching on
P0-15
Automatic start-up delay
on power-up
0,0 - 100,0
0.1s
5.0
☆
P0-16 Freeze protection
0: off
1: on
1
0
☆
P0-17
Operating frequency of
freeze protection
0.0 - 50
0.01Hz
10.00
☆
P0-18
Operating time of freeze
protection
0 - 1000
1s
60
☆
P0-19
Operating cycle of
freeze protection
0 - 1000
1s
300
☆
When set to 0, it will always run at
the anti-freeze operating frequency
P0-20 Water leakage factor
0,0 - 100,0
0.1
1.0
☆
The larger the leakage, the larger
the coefficient
P0-21
High pressure alarm
setpoint
0,0 - P0.08
0.1bar
9.0
☆
When the feedback pressure is
greater than or equal to this setpoint,
the alarm is triggered and stopped
after a delay of P0-22
P0-22
High pressure alarm
detection time
0,0 - 120,0
0.1s
3.0
☆
P0-23
Low pressure alarm
setpoint
0,0 - P0.00
0.1bar
0.0
☆
When the feedback pressure is lower
than the set value, the alarm is
triggered after a delay of P0-24.If set
to 0, this function is invalid.
P0-24
Low voltage alarm
detection time
0,0 - 120,0
0.1s
3.0
☆
P0-25 Dry running protection
0: Off
1: Water shortage
evaluation by frequency
and current
2: Evaluation by
frequency and pressure
1
2
☆