Page
76
When P211, 221, 231, 241, 251, 261, 271, 281, 291, 571 =10 (RMA Alarm)
P213, P223, P233, P243, P253, P263, P273, P283, P294, P573
Relay Alarm Setpoint
This parameter determines the RMA alarm
ON/OFF
point, this is the
rate of
change during pumping
at which a potential
burst
or
blockage
condition may
occur (depending on Relay Alarm ID). Units are in rate measurement units and
are dependent on
P116 Rate Method
.
P214, P224, P234, P244, P254, P264, P274, P284, P294, P574
Relay Setpoint 2
This parameter determines the “
Persistence Time
”. This is the amount of time
the rate has to
persist
above/below the
Alarm Setpoint
(P213, 223, 233, 243,
253, 263, 273, 283, 293, 573) before the alarm will change state. It is used to
prevent relay “chatter” if the rate is near the alarm setpoint. Units are in
Seconds
.
P215, P225, P235, P245, P255, P265, P275, P285, P295, P575
Relay Setpoint 3
This parameter determines the “
Prime Head
Level
”. The RMA function will not
raise
an alarm below this level but will allow an alarm to turn off. Units are in
Measurement Units (P104).