To program the Quantum
3
for
Example 2 Sump control (pump down) b
y
using the
Quick Setup
menu proceed as follows.
If required access the
Program Mode
Key in the
passcode
1997
and press
ENTER
At the
Quick Setup
menu press
ENTER
and as prompted, by the questions,
select the relevant option and
ENTER
.
Question
Option
Level/Pump/Custom
2=Pump Down
No. of Pumps
2=2 Pumps
Pump Duty
3=Alt DutAss
Pump No 1
1 = Set Relay 1
Pump No 2
2 = Set Relay 2
No. of Alarms
1=1 Alarms
Type Alarm 1
1=High Alarm
Alarm No 1
5 = Set Relay 5
Xducer (P101)
2=dB6
Measnt Units (P104)
1 = metres
Empty Level (P105)
3.5 (metres)
Span (P106)
2.8 (metres)
Programming is now complete and the unit can be returned to the run mode,
press
CANCEL
until
Run Mode?
Is displayed on the LCD press
ENTER
,
and the Quantum
3
will return to the
Run Mode
.
Note
If relay setpoints do not meet the exact requirements of the application, they
can be modified to suit by pressing ENTER when, “For More Options Hit
Enter”, is displayed, and entering new values to relay setpoints as required.
Alternatively, the relevant relay setpoint can be accessed either by the main
menu system or directly via parameter number and changed as necessary.