Page
144
Setpoint
By
default,
the mA Output will represent the
empty
(
0
or
4mA
dependant on
(
P830
)
mA Range
) and
100%
of the operational
span
(
20mA
), but you may
wish to have the output represent a section of the operational span. For
example, the application has an operational span of 6 metres but
output
is to
represent
empty
(
0
or
4mA
dependant on
(
P830
)
mA Range
) to a
level
of
5
metres
(
20mA)
. If so P834 (Low Level) should be set to 0.00 metres and
P835 (High Level) should be set to 5 metres.
P834 mA Low Value
This parameter sets, in
Measurement Units (P104)
the value of ‘level’,
‘distance’, or ‘space’, depending on the selected
mA Out Mode
(
P831
) at
which the low mA output will occur
(
0
or
4mA
dependant on
(
P830
)
mA
Range
)
Default = 0.000m
P835 mA High Level
This parameter sets, in
Measurement Units (P104)
the value of ‘level’,
‘distance’, or ‘space’, depending on the selected
mA Out Mode
(
P831
) at
which the high mA output will occur
(
20mA
).
Default = 6.000m
Limits
P836 mA Low Limit
This parameter sets the lowest value that the mA output will drop to, the
default is 0mA, but you can override this if the device you connect to cannot
for example accept less than 2mA, yet you want to use the 0-20mA range.
Default = 0.00mA
P837 mA High Limit
This parameter sets the highest value that the mA output will rise to, the
default is 20 mA, but you can override this if the device you connect to cannot
for example accept more than 18 mA, yet you want to use the 0-20 mA range.
Default = 20.00mA