P210, P220, P230, P240, P250, P260, P270, P280, P290, P570
Relay Type
This parameter defines what type each relay should be, see the table below
for available options.
Option
Description
0= Not In Use (Default)
Relay not programmed, and LED will always
be off.
1= Alarm
Relay is programmed as an alarm relay,
which will
de-energise
to switch the alarm
ON
, and
energise
to switch the alarm
OFF
.
This will ensure an alarm is raised if the
power fails to the unit.
2= Pump
Relay is programmed as a pump relay, which
will
energise
to
switch the pump
ON
, and
de-energise
to switch the pump
OFF
.
3= Control
Relay is programmed as a control relay,
which will
energise
to
switch
ON
, and
de-
energise
to
switch
OFF
.
4= Miscellaneous
Relay is programmed as a miscellaneous
relay, which will
energise
to
switch
ON
, and
de-energise
to
switch
OFF
.
5= Pump by time
Relay is programmed as a pump relay, which
will energise at its
ON level
setpoint, and de-
energise at its
OFF level
setpoint or after a
predetermined
time
period,
whichever
occurs first.