Input Function
Individual inputs can be configured for any one of a number of
Functions
as
determined by
P373, 376, 379, 382, 385, 388, 391
these functions are as
follows:
1 = Device Fail
input will provide a signal indicating a “failure” or the
presence of a “run” signal from the device. When using
digital inputs to detect a “run” condition the input is
assumed to be in its operational status until the expiry
of
P304 Input Delay
which is used to determine the
delay time that occurs from the time that the device is
called to “run” and the digital input providing a signal
appropriate to its operational status.
2 = Duty
input will provide a signal to manually select the lead
device.
3 = Override ON
input will provide a signal to override all selected pump
setpoints “ON”.
4 = Override OFF
input will provide a signal to override all selected pump
setpoints “OFF”.
5 = Reset
input will provide a signal to reset all Device Fail
signals.