www.pulsar.pl
PSBEN1012B/LCD
28
Optical indication:
- LEDs on the PSU’s pcb,
- LCD panel
•
electrical parameters reading
•
failure indication
•
PSU settings adjusted from the panel’s level
•
3 levels of access, password-protected
•
PSU operation history – 6144 values
•
failure history - 2048 events
•
real-time clock, battery-backed
Acoustic indication:
- piezoelectric indicator ~75dB /0,3m, switched via jumper
LCD display’s battery
3V,
lithium
, CR2032
F
BAT
fuse
F
MAIN
fuse
F 2,A / 250V
T 0,315A / 250V
Table 11. Mechanical specifications.
Enclosure dimensions
270 x 250 x 88 (275 x 255 x 80+8) (WxHxD) [mm] (+/- 2)
Fixing
245 x 223 x
Φ
6 x4 (WxH)
Fitting battery
7Ah/12V (SLA) max.
Net/gross weight
3,0/3,2 kg
Enclosure
Steel plate DC01 1mm, colour RAL 9005 (black)
Closing
Cheese head screw x2 (at the front), lock assembly possible
Connectors
Supply:
Φ
0,63÷2,50 (AWG 22-10)
Outputs :
Ф
0,51÷2 (AWG 24-12),
Battery outputs BAT: 6,3F-2,5, 30cm,
TAMPER output: wires, 25cm
Notes
The enclosure does not adjoin the assembly surface so that cables can be led.
Convectional cooling.
Table 12. Operation safety.
Protection class PN-EN 60950-1:2007
I (first)
Protection grade PN-EN 60529: 2002 (U)
IP20
Electrical strength of insulation:
- between input (network) circuit and output circuits of the PSU (I/P-O/P)
- between input circuit and PE protection circuit (I/P-FG)
- between output circuit and PE protection circuit (O/P-FG)
3000 V/AC min.
1500 V/AC min.
500 V/AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 M
Ω
, 500V/DC
Table 13. Operating specifications.
Operating temperature
-10ºC...+40ºC
Storage temperature
-20ºC...+60ºC
Relative humidity
20%...90%, without condensation
Vibrations during operation
unacceptable
Impulse waves during operation
unacceptable
Direct insolation
unacceptable
Vibrations and impulse waves during transport
PN-83/T-42106
Table 14. PSU’s factory settings.
Indication time of EPS network loss
5s
Battery charging current
0,6A
Battery presence
YES (battery present)
Battery test
YES (activated)
Deep discharge battery protection UVP
YES (battery protected)
Communication address
1
Transmission
19.2k 8E1
Highlighting
Constant – 50%
Passwords:
- keypad’s
- user’s
- installer’s
(n/a)
1111