The  main panel of the program has been formulated in such a way that it is possible to divide it into smaller 

areas, depending on the number of power supplies.  

The program enables both a visualisation and an analysis of the received data. Exceeding of the acceptable 

parameters  is indicated  by  highlighting  in  red  the  appropriate  area or  by  twinkling  of  the  indicator.  Particular  tabs 
contain a chart with an overview of the PSU parameters and failure  memo along with the information about status 
and the electrical specifications of the technical outputs. 

 

The ”Power Security” program is available on our website: 

www.pulsar.pl

  

Its detailed description can be found in the manual of the program. 

 

 
6. Technical specifications.  

Electrical specifications (tab.10). 
Mechanical specifications (tab.11). 
Operation safety (tab.12). 
Operating specifications (tab.13). 
Factory settings (tab. 14). 

 

Table 10. Electrical specifications. 

PSU type 

A, protection grade 1÷3, II environmental class 

Mains supply 

230V/AC  (-15%/+10%) 

Current consumption 

0,13 A  

Power frequency 

50Hz 

PSU’s power 

17 W 

Efficiency 

72% 

Output voltage 

11,0V÷13,8 V DC – buffer operation 
10,0V÷13,8 V DC – battery-assisted operation 

Output current 

- for grades 1, 2:  

 

 

 

Io = 0,58A + 0,6A battery charge 

- for grade 3: 

 

 

Io = 0,23A + 0,6A battery charge - (connection with 

ARC required, compliant with 9.2 – PN-EN 50131-1) 
 

Io = 0,116A + 0,6A battery charge 

- for general use: 
 

Io = 1A + 0,2A battery charge 

 

Io = 0,6A + 0,6A battery charge 

Output voltage setting, escalation and keeping 
time 

10ms / 34ms / 12ms 
 

Output voltage adjustment range 

12 V÷ 14,5 V  

Ripple voltage 

30 mV p-p max. 

Current consumption by the PSU systems 
during batter-assisted operation 

I = 26mA  
I = 17 mA – highlighting of the LCD desktop is off 

Battery charging current 

0,2A / 0,6A –I

BAT 

jumper selectable

 

Low battery voltage indication 

Ubat < 11,5V, 

during battery-assisted operation

 

Over voltage protection OVP 

U>15,5V, 

disconnection of the output voltage, automatic return 

(AUX+ disconnection)

 

Short circuit protection SCP 

200% ÷ 250% 

of the PSU power - current limiting and/or fuse 

fault in the battery circuit (fuse-element replacement required)

 

Overload protection OLP 

Program - equipment 

Battery circuit protection SCP and reverse 
polarity connection 

F2 A- 

current limiting, F

BAT

 fuse (failure requires fuse-element 

replacement)

 

Deep discharge battery protection UVP 

U<10,0 V (± 2%) – 

disconnection (-BAT) of the battery, 

adjustment from the 

LCD desktop’s level 

- type – electronic, max 50mA/30V DC, galvanic isolation 
1500V

RMS

 

time lag, approx. 

5s/140s/17m/2h 20m (+/-5%) 

- type – electronic, max 50mA/30V DC, galvanic isolation 
1500V

RMS

 

- type – electronic, max 50mA/30V DC, galvanic isolation 
1500V

RMS

 

Technical outputs: 

- EPS FLT; 

output indicating AC power failure 

 
- APS FLT; 

output indicating battery failure 

 
- PSU FLT; 

output indicating PSU failure  

 
- TAMPER output indicating enclosure opening 
and 

detachment

 from the mounting surface 

- microswitches x2, 

NC contacts (enclosure closed and fixed to 

the mounting surface)

, 0,5A@50V DC (max.) 

EXT IN technical input 

Voltage ’on’ –  10

÷

30V DC 

Voltage ’off’ –  0

÷

2V DC 

Level of galvanic isolation: 1500V

RMS

 

Summary of Contents for PSBEN 1012B/LCD

Page 1: ...PSBEN 1012B LCD v 1 0 PSBEN 13 8V 1A 7Ah EN LCD Buffer switched mode power supply unit EN Edition 3 from 20 11 2012 Supersedes the 2 from 14 09 2012 edition...

Page 2: ...ing the EPS output lag 16 Setting the communication address 17 3 4 3 Desktop 17 Setting the language of messages 18 Setting the date 18 Setting the time 19 Setting the highlighting 19 Setting the cont...

Page 3: ...QUIREMENTS 29 7 2 INSTALLATION PROCEDURE 29 8 OPERATION AND USE 30 8 1 OVER VOLTAGE PROTECTION OVP AT THE PSU OUTPUT 30 8 2 OVERLOAD OF THE PSU 30 8 3 SHORT CIRCUIT AT THE PSU OUTPUT 30 8 4 BATTERY RE...

Page 4: ...ory real time clock battery backed optical indication of PSU overload OVL acoustic indication of failure adjustable times indicating AC power failure technical inputs outputs with galvanic isolation c...

Page 5: ...time 60h if the faults of the main power source are reported to the Alarm Receiving Centre ARC in accordance with 9 2 PN EN 50131 1 Output voltage 0 116A 0 6A battery charge General use if the PSU is...

Page 6: ...off 6 VADJ potentiometer DC voltage adjustment 7 BUZZER acoustic indicator 8 FBAT fuse in the battery circuit 9 Connectors AC AC power input BAT DC power battery output AUX DC power output AUX U AUX...

Page 7: ...N 230V AC power connector PE connector 6 Battery connectors positive BAT red negative BAT black 7 Grip of tamper resistance Fig 3 The view of the PSU 3 Operating status indication 3 1 Control panel T...

Page 8: ...lay The main screen of the LCD display shows basic electrical parameters and informs about the current PSU state Fig 5 The main screen Table 4 Description of the symbols on the main screen Screen fiel...

Page 9: ...tatus during operation Highlighting of an element informs about an active state and reflects the status of LEDs on the pcb of the PSU see table 1 12 Fig 7 Screen parameters of the PSU Table 5 Descript...

Page 10: ...analysis of the values shown on the chart the time range of the chart screen can be adjusted in the bottom axis Here are the available ranges 8h 24h 2days week weekly In order to change the displayed...

Page 11: ...erates 3 levels of access to configuration which limit the possibility of changing the PSU s settings from the level of the LCD desktop They are protected with separate passwords Keypad password locks...

Page 12: ...ear with or choose the right level of the password confirm your choice with the SET button with or enter the first digit confirm your choice with the SET button with or enter the second digit confirm...

Page 13: ...swords have been lost there is a procedure that will allow reassigning the passwords Please do as follows a unplug the PSU from the AC network and the battery for at least 10 seconds b press the STOP...

Page 14: ...to the PSU NO battery not connected to the PSU see chapter 4 6 Battery test YES battery test on NO battery test off see chapter 4 3 Battery protection YES battery protection function disconnection on...

Page 15: ...onfirm your choice with the SET button Setting the battery test with or choose the Battery test menu press the SET button you will see the prompt at the end of the line with or set YES or NO YES batte...

Page 16: ...nction disconnection on NO battery protection function disconnection off confirm your choice with the SET button Setting the EPS output lag with or choose the EPS output lag menu press the SET button...

Page 17: ...mputer confirm your choice with the SET button 3 4 3 Desktop The facility is only available after entering the correct user s or installer s password The Desktop menu enables setting the current date...

Page 18: ...you will see the prompt at the end of the line with or choose the language of messages confirm your choice with the SET button Setting the date with or choose the Date menu press the SET button the pr...

Page 19: ...ection with or set the minutes press the SET button the prompt will move to the second section with or set the seconds approve the settings with the SET button Setting the highlighting Intensity of th...

Page 20: ...t to the constant option with or change the setting into 60 s press the SET button the prompt will move to the end of the line with or set the demanded screen brightness approve your choice with the S...

Page 21: ...e In case of a power failure the PSU will switch the output into the open state after a period of time determined by the EPS output lag facility see 3 4 2 table 7 APS FLT output indicating battery fai...

Page 22: ...IN technical input has been implemented with galvanic isolation between the PSU s systems and the devices attached Fig 16 Electrical diagram of the EXT IN input The electrical diagram below shows the...

Page 23: ...ry test facility can be switched off Deactivating activating the test enter the PSU settings from the level of the LCD desktop by pressing the SET button Then choose PSU Battery protection YES NO see...

Page 24: ...AT jumper 10h30m 0 6 31h30m 0 2 4 6 Operation without a battery In case of an expected PSU operation without an attached battery make a necessary configuration setting from the level of the LCD deskto...

Page 25: ...age of wireless communication is lack of additional cords and fast development or modification of the network s structure Fig 19 WI FI communication with the use of the WI FI INTW interface 5 2 Commun...

Page 26: ...USB TTL INTU needs to be used This interface allows direct connection between the computer and the PSU and it is recognisable by the operating system as a virtual COM port Fig 22 USB TTL communicatio...

Page 27: ...0 6A 0 6A battery charge Output voltage setting escalation and keeping time 10ms 34ms 12ms Output voltage adjustment range 12 V 14 5 V Ripple voltage 30 mV p p max Current consumption by the PSU syste...

Page 28: ...ables can be led Convectional cooling Table 12 Operation safety Protection class PN EN 60950 1 2007 I first Protection grade PN EN 60529 2002 U IP20 Electrical strength of insulation between input net...

Page 29: ...3 7 and guarantees indication in case of any attempts of detaching the device from the mounting surface Proper installation is one of the requirements of the PN EN 50131 6 standard Fig 24 Fixing a ta...

Page 30: ...output status change opening state acoustie and appropriate message on the PSU front panel 8 2 Overload of the PSU The PSU has been equipped with a LED OVL overload indicator light on the pcb It info...

Page 31: ...igh output voltage Output voltage 14 7V F07 ON 2 flashes ON PSU FLT Too high battery voltage Battery voltage 14V F08 ON 3 flashes ON PSU FLT Battery charging circuit failure Too low output voltage of...

Page 32: ...ssibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are car...

Reviews: