4. Battery-assisted operation.
4.1. Running the PSU from the battery.
The PSU has been equipped with two buttons on the pcb board which enable running or disconnecting the
PSU during battery-assisted operation.
•
Running the PSU from the battery: press the START button on the main board and hold for 1s.
•
Disconnecting the PSU from the battery: press the STOP button on the main board and hold for 5s.
4.2. Deep discharge battery protection UVP.
The PSU is equipped with the disconnection system and the discharged battery indication. If the voltage at
the battery terminals drops below 10V±0.2V during battery-assisted operation, the battery will be disconnected
after appr.15s.
Switching off/on the function of the battery protection:
Press the ‘SET’ button from the level of the LCD desktop and then choose:
”PSU -> Battery protection: YES/NO”
(see chapter 3.4.2, table 7).
Caution.
Deactivating of the UVP function is not recommended since a deep discharge of the battery limits its
capability of storing energy, lowers its capacity and shortens its durability.
4.3 Dynamic battery test.
The PSU runs a battery test every 10 minutes. It is done by a momentary switching into a battery-assisted
operation. A failure is indicated when voltage drops below 12V. The battery test facility can be switched off.
Deactivating/activating the test:
- enter the PSU settings from the level of the LCD desktop by pressing the ‘SET’ button. Then choose:
”PSU -> Battery protection: YES/NO”
(see chapter 3.4.2, table 7) or
- from the pcb level: during mains-powered PSU operation press the STOP button on the main board and
hold it for 3 seconds.
The device will confirm the activation/deactivation of the test (see tab.8 [6, 7]) and show an appropriate
message on the display:
”TEST ON/ TEST OFF”
.
Deactivating/activating the test is stored in the memory even after unplugging the device from
mains. The battery failure indication at the APS FLT output is automatically switched off. The
battery protection system against deep discharged remains on, though.
4.4. Standby time.
The standby time during batter-assisted operation depends on: battery capacity, battery charge level and
load current. In order to keep the standby time, the current drawn from the PSU during battery-assisted operation
should be limited. Characteristics for a 7Ah/12V SLA:
Grade 1, 2 - standby time 12h
Output current 0,58A + 0,6A battery charge
Grade 3 - standby time 30h if the faults of the main power source are reported to the Alarm Receiving
Centre - ARC (in accordance with 9.2 – PN-EN 50131-1).
Output current 0,23A + 0,6A battery charge
- standby time 60h if the faults of the main power source are reported to the Alarm Receiving
Centre - ARC (in accordance with 9.2 – PN-EN 50131-1).
Output current 0,116A + 0,6A battery charge