background image

www.pulsar.pl                                                      POE164864   

                         

GREEN POWER CCTV PoE

 

 

 

 

 

 

Rys. 5. Connection of cameras and network devices to the IN and AUX terminals. 

 

6. Use the F1/PTC1 

– F16/PTC16 jumpers to select the type of short circuit / overload protection of individual 

circuits. Jumper in the Fx position 

– melting fuse activation, PTCx – PTC fuse activation.  

7. If needed, the following technical connections can be made: 
- FPS technical output of the PSU status 

– indicates the voltage loss at any of the outputs (AUX1 ÷ AUX16). 

TAMPER

 indicating enclosure opening. 

8. Check the optical indication of the PSU status: green LED light on the PoE module. 
9. In cas

e of significant voltage drops on the receivers’ power cables resistance, it is possible to adjust the voltage 

with the V

ADJ

 potentiometer 

(41÷56V DC). 

10. Close the cover after installing and checking the operation of the power supply.

 

 
 
3.  Power supply operation indication. 

 

3.1. Optical indication. 

The PSU has 16 LED lights at the front panel: 
 

 

 

 
 

 

 
 

 

 
RED LED: 

 

on 

– DC voltage at the output of the switch mode PSU  

 

off 

– no DC voltage at the output of the switch mode PSU 

 
RED LED: 

 

on 

– fuse failure at one of the AUX1…AUX16 outputs 

 

off 

– no failure 

 

 
 
GREEN LED: 

 

on 

– DC voltage at the AUX1…AUX16 output 

 

off 

– no DC voltage at the AUX1…AUX16 output 

 

 

Additionally, the PSU is fitted with LED lights inside the enclosure 

– see Fig. 2 and 3: 

L

IN

 green LED (Fig. 2, component 1) indicates DC voltage at the PoE module input. During normal operation (DC 

supply) the LED is permanently illuminated. No DC no DC voltage at the module input is indicated by turning off the 

L

IN 

LED.  

L

FPS

 

red LED (Fig. 2, component 10) is not illuminated during normal operation (no failure). In case of activation of 

the short circuit / overload protection at any output, the LED is permanently illuminated.  

L1 ÷ L16

 green LEDs (Fig. 2, component 5) indicate voltage at the individual outputs of the module (L1 for AUX 1 

etc.). Activation of the short circuit / overload protection of a given circuit is indicated by turning off one of the Lx  
LEDs.  
 
 
 
 

Summary of Contents for POE164864

Page 1: ...POE164864 v 1 0 PoE 48V 16x0 4A Switch mode power supply unit for CCTV EN Edition 1 from 01 12 2014 Supersedes the edition GREEN POWER CCTV PoE...

Page 2: ...ation 3 2 Technical outputs 4 Service and operation 4 1 Overload or short circuit of the power supply output 4 2 Maintenance 1 Technical description 1 1 General description The PSU is designed for sup...

Page 3: ...uses in the AUX1 AUX16 F 500mA circuits 4 Jumper to select melting fuse or PTC polymer fuse 5 Green LED L1 L16 voltage indication at the AUX outputs during normal operation these LEDs are on 6 Network...

Page 4: ...www pulsar pl POE164864 GREEN POWER CCTV PoE 4 Fig 2 Components arrangement...

Page 5: ...tion of the power supply output voltage 5 PoE module 6 Plate for mounting the network switch Ethernet switch hub 7 TAMPER microswitch contacts of antisabotage protection NC Tab 2 Components of the PSU...

Page 6: ...wires 35cm Notes The enclosure has a 15mm distance from the mounting surface so the cables can be led PSU cooling fan cooling Safety of use Table 5 Protection class PN EN 60950 1 2007 I first Protect...

Page 7: ...ore installation cut off the voltage in the 230V power supply circuit 2 Mount the PSU in a selected location and lead the connecting cables 3 If required mount the switch network Ethernet Switch Hub o...

Page 8: ...cal indication The PSU has 16 LED lights at the front panel RED LED on DC voltage at the output of the switch mode PSU off no DC voltage at the output of the switch mode PSU RED LED on fuse failure at...

Page 9: ...pening volt free contact input indicating the status of the power supply doors PSU closed contacts closed NC PSU open contacts open NO 4 Service and operation 4 1 Overload or short circuit of the powe...

Page 10: ...here are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services are carried out a...

Reviews: