background image

www.pulsar.pl                                                      POE164864   

                         

GREEN POWER CCTV PoE

 

 

 

 

      
During normal operation, the total current drawn by the device should not exceed  

I = 16x0,4A.  

 

 
The    power    supply    is    designed    for    a    continuous    operation    and    is    not    equipped    with    a    power-

switch. Therefore, an appropriate overload protection in the power supply circuit should be provided. Moreover, the 
user should be informed how to disconnect the power supply unit from the mains supply (usually by assigning an 
appropriate  fuse  in  the  fuse  box).      The  electrical  system shall  be  made  in  accordance  with applicable  standards 
and regulations.  

The PSU is designed for 10Mbit/s and 100Mbit/s  Ethernet network (so-called Fast Ethernet)

. However, it 

can  not  be  used  for  a  1000  Mbit/s  network  (so-called  Gigabit  Ethernet).

  Connections  between  the  power 

supply and the camera can be done using UTP-3 cable (networks with data-rates up to 10 Mbit/s) or UTP-5 cable. 
Due to the lower resistance wiring, it is recommended (especially at large distances between the power supply and 
receivers) to use UTP-5 cable also for networks with data-rates up to 10 Mbit/s.  

 

2.2. Installation procedure. 
 

1. Before installation, cut off the voltage in the 230V power-supply circuit. 

2. Mount the PSU in a selected location and lead the connecting cables. 
3. If required, mount the switch network (Ethernet Switch / Hub) on the mounting plate (element 6, Figure 3) using 
cable  ties  supplied  with  the  PSU.  An  example  of  mounting  the  Ethernet  switch  is  shown  in  Figure  4: 
 

 

 

 Fig.4. An example of mounting the Ethernet switch. 

 

4.  Connect  the  power  cables  (230V  AC)  to  L-N  terminals  of  the  PSU.  Connect  the  ground  wire  to  the  terminal 

marked  with grounding  symbol:

.  Use  a  three-core  cable  (with a  yellow  and  green  PE  protection  wire)  to make 

the  connection.  The  power  cables  should  be  connected  to  the  appropriate  terminals  on  the  connection  board 
through the bushing.  

 

 

The shock protection circuit shall be done with a particular care: the yellow and green wire 

coat of  the  power  cable  should be connected to  the  terminal  marked  with  the  

  symbol  

in  the  PSU enclosure. Operation of the PSU without the properly made and fully operational 
shock  protection  circuit  is  UNACCEPTABLE!  It  can  cause  damage  to  the  equipment  or  an 
electric shock

 

 
5.  Connect  the  network  cables  (Ethernet)  to  the  PoE  module:  supply  voltage  is  present  only  at  the  AUX  sockets 
and the cameras should be connected to them. Pin assignment of the AUX and IN sockets is shown in the Figure 
5:  
 
 
 
 
 
 
 
 

Summary of Contents for POE164864

Page 1: ...POE164864 v 1 0 PoE 48V 16x0 4A Switch mode power supply unit for CCTV EN Edition 1 from 01 12 2014 Supersedes the edition GREEN POWER CCTV PoE...

Page 2: ...ation 3 2 Technical outputs 4 Service and operation 4 1 Overload or short circuit of the power supply output 4 2 Maintenance 1 Technical description 1 1 General description The PSU is designed for sup...

Page 3: ...uses in the AUX1 AUX16 F 500mA circuits 4 Jumper to select melting fuse or PTC polymer fuse 5 Green LED L1 L16 voltage indication at the AUX outputs during normal operation these LEDs are on 6 Network...

Page 4: ...www pulsar pl POE164864 GREEN POWER CCTV PoE 4 Fig 2 Components arrangement...

Page 5: ...tion of the power supply output voltage 5 PoE module 6 Plate for mounting the network switch Ethernet switch hub 7 TAMPER microswitch contacts of antisabotage protection NC Tab 2 Components of the PSU...

Page 6: ...wires 35cm Notes The enclosure has a 15mm distance from the mounting surface so the cables can be led PSU cooling fan cooling Safety of use Table 5 Protection class PN EN 60950 1 2007 I first Protect...

Page 7: ...ore installation cut off the voltage in the 230V power supply circuit 2 Mount the PSU in a selected location and lead the connecting cables 3 If required mount the switch network Ethernet Switch Hub o...

Page 8: ...cal indication The PSU has 16 LED lights at the front panel RED LED on DC voltage at the output of the switch mode PSU off no DC voltage at the output of the switch mode PSU RED LED on fuse failure at...

Page 9: ...pening volt free contact input indicating the status of the power supply doors PSU closed contacts closed NC PSU open contacts open NO 4 Service and operation 4 1 Overload or short circuit of the powe...

Page 10: ...here are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services are carried out a...

Reviews: