Page
88
Modbus Functions
Function 1: Read Output Status
Registers Address
Description
Data Type
Unit/Range
00001 – 00006
Relay status
Bit mapped
None
Note
1.
Bit value of
1
represents an
ACTIVE STATE
of the
corresponding relay.
2.
Bit value of
0
represents an
IN-ACTIVE STATE
of the
corresponding relay.
Example:
Query: reading relay 2 to 4
Slave address
11
Function
01
Addr Hi
00
Addr Lo
02
No. of points hi
00
No. of points lo
03
Error check
Response: relay 2 = on, relay 3 = off, relay 4 = on
Slave address
11
Function
01
Byte count
01
Data (coil 2-4)
0a
Error check