P102 Material
This parameter should be set to monitor the type of material being monitored.
Option
Description
0 = Liquid
(Default)
Use for liquids and flat solid materials
1 = Solid
Solid material that is heaped or at an angle
2 = Closed tank
Use for applications within a closed tank or where a
secondary echo response may become focused to
create a larger echo than the first.
Dimensions
P104 Measurement Units
This parameter sets the units you want to use for programming and display
Option
Description
1 = metres (Default)
All units of measure are
METRES
2 = cm
All units of measure are
CENTIMETRES
3 = mm
All units of measure are
MILLIMETRES
4 = feet
All units of measure are
FEET
5 = inches
All units of measure are
INCHES
P105 Empty Level
This parameter is to be set to the maximum distance from the face of the
transducer to the
empty point
, in
P104
Measurement
Units
. Note this value
affects span as well, (see important information below), so should be set
before span.
Important Information
When changing the Empty Distance (P105) you can also recalculate
the values for the Span so that it equals the empty distance (P105)
minus Near Blanking (P107) and the Relay Setpoints, so that they
remain at the same percentage values of the empty distance as they
were before you changed the empty distance (P105). You will be asked
the question “Recalculate Span?” if you choose yes (enter 1), then the
span will be recalculated. Any other answer will leave the span at its
original value. You will then be asked if you want to “Recalculate
Setpoints?”, if you choose Yes (enter 1), then all Relay Setpoints will
be recalculated as a percentage of the new empty distance. Any other
answer will leave the setpoints at their original values.
Summary of Contents for blackbox 134
Page 1: ...blackbox 134 INSTRUCTION MANUAL...
Page 2: ......
Page 4: ......
Page 8: ...Chapter 9 Disposal 105 Parameter Record 107...
Page 14: ...Page 6 EU Declaration of Conformity...
Page 18: ...Page 10 Large Enclosure optional The dimensions of the mounting holes are as shown below...
Page 26: ...Page 18 This page left blank intentionally...
Page 40: ...Page 32 This page left blank intentionally...
Page 112: ...Page 104 This page left blank intentionally...