Page
96
Function 16: Write Multiple Registers (Static Parameters)
Registers
Address
Description
Unit/Range
40100 – 40999
(1)
Set up parameters
(2)
(3)
Note
1.
Only parameters from P100 to P999 are available for writing
from remote communication. Parameters less than P100 have to
be accessed directly on the unit keypad or infra-red
communicator
2.
Refer to Chapter 7 List of Static Parameters for list of accessible
parameters.
Example: Query: writing to P100 = 1, P101=2
Slave address
11
Function
10
Addr Hi
00
Addr Lo
64
No. of registers hi
00
No. of registers lo
02
Data Hi
00
Data Lo
01
Data Hi
00
Data Lo
02
Error check
Response:
Slave address
11
Function
06
Addr Hi
00
Addr Lo
64
No. of registers hi
00
No. of registers lo
02
Error check