7
5
Features, Benefits, Specifications
5.1
Features
ORP input with ORP sensor diagnostics indicates fouled reference or open PT band.
Conductivity input with fouling compensation and alarm.
Integral flow sight & flowswitch lockout.
Two (2) water meter inputs. Records both makeup (
MTR1
) and Blowdown (
MTR2
) water meter total
gallons.
Configure Blowdown water meter (
MTR2
) as second makeup meter.
One relay configured for bleed off and three user configurable relays for conductivity or pH control and
chemical addition. These relays can be configured in multiple ways including scheduled feed for biocide
addition
Blowdown Relay options:
Bleed x gallons for every x gallons makeup
Bleed x minutes for every x gallons of makeup
Bleed by setpoint
Bleed by cycles of concentration with
NCON/NCKT
Option
Bleed by multi-setpoint selected with
NCON/NCKT
Option
User-selectable relay options:
Feed by setpoint, direct or reverse
Water meter actuated feed.
MTR1
,
MTR2
or the sum of the two
Percent of blowdown time
Percent of Time feed
Calendar Timer timer
General alarm
Three security levels: View only, operator, technician
4-20 mA output available as an option.
Remote communications available as an option.
16-key numeric keypad and illuminated graphical display allow for quick and easy programming.
The Model 3323 controller stores all setpoints, calibration values, and relay configurations in an
EEPROM. An EEPROM does not require a battery to retain information, so if power is lost these values
will be retained for years. The 3323 includes a battery backup device to retain information such as water
meter totals, and clock and calendar information. Battery life is approximately 3 months if no power is
applied to the controller.
5.2
Benefits
Multiple control options in a single economical package.
Very accurate control of chemical feed and cycles of concentration.
Feeds chemical after blowdown.
Very low maintenance.
Tolerant to power surges and brownouts.
Power cord, plug outlets and attached plumbing make installation easy. There is plenty of protected
room inside the enclosure for electrician wiring.
Very accurate monitoring of the evaporated water.