background image

 

 

YR40.245

 

 

Y-Series 

12-28V,

 

40A,

 

S

INGLE 

R

EDUNDANCY 

M

ODULE

 

 

 

5.

 

L

IFETIME 

E

XPECTANCY AND 

MTBF 

 

Load conditions 

Output: 20A 

Output: 40A 

 

Lifetime expectancy

 *)

 557 

000h

 *)

 134 

000h

 *)

 

at 24V and 40°C 

 

1 576 000h

 *)

 378 

000h

 *)

 

at 24V and 25°C 

MTBF

 **)

  SN 29500, IEC 61709 

13 290 000h 

6 357 000h 

at 24V 40°C 

 

22 628 000h 

12 238 000h 

at 24V 25°C 

MTBF

 **)

  MIL HDBK 217F 

381 000h 

278 000h 

Ground Fixed GF40 (24V and 40°C) 

 

518 000h 

366 000h 

Ground Fixed GF25 (24V and 25°C) 

 

1 816 000h 

1 401 000h 

Ground Benign GB40 (24V and 40°C) 

 

2 486 000h 

1 861 000h 

Ground Benign GB25 (24V and 25°C) 

*)   The 

Lifetime expectancy

 shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime 

expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the 
capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years 
(131 400h). Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices. 

**) 

MTBF

 stands for 

M

ean 

T

ime 

B

etween 

F

ailure, which is calculated according to statistical device failures, and indicates reliability of a 

device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product. 

 

The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that 
statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not be determined if the failed unit 
has been running for 50 000h or only for 100h. 

 

Oct. 2013 / Rev. 1.0 DS-YR40.245-EN  
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted 

www.pulspower.com   Phone +49 89 9278 0    Germany 

6/18

Summary of Contents for DIMENSION Y-Series

Page 1: ...ry voltage Due to the low power losses the unit is very slender and only requires 46mm width on the DIN rail Large connection terminals allow for a safe and fast installation The large international a...

Page 2: ...before the value represents a nominal voltage with standard tolerances usually 15 included E g DC 12V describes a 12V battery disregarding whether it is full 13 7V or flat 10V 24Vdc A figure with the...

Page 3: ...ed permanently with more than 50 of the rated output current Increase the side clearance to 15mm in case the adjacent device is a heat source e g another power supply See chapter 19 3 for other allowe...

Page 4: ...22A in overload voltage 6V or short circuit mode Reverse current max 1mA at 24V per input 40 C to 70 C Reverse voltage max 40Vdc voltage applied to the output continuously allowed Output capacitance t...

Page 5: ...equal current Power Losses typ 0 0 5 10 30 1 4 5 8W 40A 25 15 20 35 Output Current A 2 6 B 7 A 24V 25 C B 24V 60 C 3 V A QS40 set to 24V IIN UIN Output A V IOUT UOUT Variable Load 0 40A YR40 245 Input...

Page 6: ...r specification The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years 131 400h Any number exceeding this value is a calculated theoretical lifetime which can...

Page 7: ...60950 1 SELV b Use appropriate copper cables that are designed for minimum operating temperatures of 60 C for ambient up to 45 C and 75 C for ambient up to 60 C and 90 C for ambient up to 70 C minimu...

Page 8: ...structions Switch off circuit breaker 3a Remove plug 4 The plug prevents the cables from shorting Change power supply 1 or and redundancy module 2 Put the plug 4 back in Turn on the circuit breaker 3a...

Page 9: ...on the top side of the housing with a ring type terminal ring cable lug which is suitable for a M4 screw Connection of the chassis is optional and not required since the unit fulfils the requirements...

Page 10: ...defined limits Notes A test is not applicable according to EN 61000 6 2 since the device does not contain components susceptible to magnetic fields e g hall elements electrodynamic microphones etc EM...

Page 11: ...ed directly from the low voltage mains IEC 60664 1 4 3 3 2 1 Degree of pollution 2 IEC 62103 EN 50178 not conductive LABS compatibility The unit does not release any silicone or other LABS critical su...

Page 12: ...hm between housing and chassis ground terminal 14 DIELECTRIC STRENGTH The input and output voltages have the same reference are floating and have no ohmic connection to ground Type and factory tests a...

Page 13: ...ation Class I Div 2 T4 Groups A B C D systems U S A ANSI ISA 12 12 01 2007 and Canada C22 2 No 213 M1987 Suitable for use in Class 1 Zone 2 Groups IIa IIb and IIc locations Number of ATEX certificate...

Page 14: ...m The DIN rail height must be added to the unit depth 127mm to calculate the total required installation depth Installation clearances See chapter 2 Fig 17 1 Front view Fig 17 2 Side view Oct 2013 Rev...

Page 15: ...eways with or without utilizing a DIN Rail The two aluminum brackets and the black plastic slider of the unit have to be detached so that the steel brackets can be mounted For sideway DIN rail mountin...

Page 16: ...on the bottom 5mm on the left and right sides when the device is loaded permanently with more than 50 of the rated power Increase this clearance to 15mm in case the adjacent device is a heat source e...

Page 17: ...lies and four YR40 245 redundancy modules Fig 19 2 Wiring diagram n 1 Redundancy 120A output current L N PE 24V 40A Parallel Use Single Use DC OK Power Supply AC Input L N PE 24V 40A Parallel Use Sing...

Page 18: ...rve A2 Max allowed output current results in approximately half the lifetime expectancy of A1 Fig 19 3 Mounting Orientation A Standard orientation YR40 245 Redundancy Module OUTPUT INPUT Output Curren...

Reviews: