UC10.241, UC10.242

 

 

UC-Series 

24V,

 

15A,

 

CAPACITOR-BASED

 

DC-UPS 

 

 

1.

 

I

NTENDED 

U

SE

 

This device is designed for installation in an enclosure. Use an appropriate enclosure which protects against 
mechanical, electrical and fire hazards. 

This device is intended for professional use in areas such as in industrial control, office, communication, and 
instrumentation equipment. 

Do not use this device in equipment or systems where malfunction may cause severe personal injury or threaten 
human life. 

 

 

2.

 

I

NSTALLATION 

N

OTES

 

This device may only be installed and put into operation by qualified personnel. 

The input must be powered from a SELV or PELV power source. 

This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect. If 
damage or malfunction should occur during installation or operation, immediately turn power off and send unit to 
the factory for inspection. 

Mount the unit on a DIN-rail so that the power terminals are located on the top of the unit. 

This device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do 
not cover ventilation grid (e.g. cable conduits) by more than 15%! 

Keep the following installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right sides are 
recommended when the device is loaded permanently with more than 50% of the rated power. Increase this clearance 
to 15mm in case the adjacent device is a heat source (e.g. a power supply). 

 

Fig. 2-1

   Typical wiring diagram 

buffered branches

non-buffered branches

3/27

 

L    N   PE

+ +

- -

Power

Supply

+

-

24V Output

UC10

DC-UPS

IN

+

-

OUT

R

ea

d

y

B

u

ff

er

in

g

In

h

ib

it

PC

-M

o

d

e

Input

+

-

 

The EDLC (storage capacitors) contain Acetonitrile and Tetraethylammonium-tetrafluoroborate. These components are 
declared as non-dangerous goods in regards to shipment. A safety datasheet can be provided when required. 

 

WARNING

  Risk of electrical shock, fire, personal injury or death. 

-  Turn power off before working on the device. Protect against inadvertent re-powering. 
-  Make sure that the wiring is correct by following all local and national codes. 
-  Do not modify or repair the unit. 
-  Do not open the unit as hazardous energy may be present inside. 

Info for service personnel: Before opening the unit, wait at least 45 minutes after disconnecting the unit from input 
power so that the remaining capacitor charge has completely been discharged. 

-  Use caution to prevent any foreign objects from entering the housing. 
-  Do not use in wet locations or in areas where moisture or condensation can be expected. 
-  Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns. 

May 2016 / Rev. 2.2 DS-UC10.241-EN 
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278 0    Germany 

Summary of Contents for DIMENSION UC Series

Page 1: ...t this energy is released to the DC bus in a regulated process The DC UPSs are maintenance free and have a similar lifetime expectancy as power supplies No regular replacement of the capacitors is nec...

Page 2: ...he publisher TERMINOLOGY AND ABREVIATIONS Normal mode Describes a condition where the capacitor is charged the input voltage is in range and the output is loaded within the allowed limits Buffer mode...

Page 3: ...permanently with more than 50 of the rated power Increase this clearance to 15mm in case the adjacent device is a heat source e g a power supply Fig 2 1 Typical wiring diagram buffered branches non b...

Page 4: ...A buffer current The transfer threshold voltage describes the input voltage where the unit switches into buffer mode and delivers output voltage from the capacitors if the input was above the turn on...

Page 5: ...15A see Fig 4 2 Short circuit current min 17 9A load impedance 100mOhm see Fig 4 2 max 21 0A load impedance 100mOhm see Fig 4 2 Output capacitance typ 1 500 F included inside the DC UPS Capacitive an...

Page 6: ...8 12 14 200mv 300mv Voltage drop Fig 4 3 Transition from buffer mode to normal mode and vice versa definitions Fig 4 4 Transfer behavior typ 500ms DIV 0V Output Voltage Input Voltage 24V 22 25V at 10...

Page 7: ...after discharging with 1A until buffering stops Allowed number of charging discharging cycles no limitation no limitation Initial charging means that no input voltage was applied for several hours or...

Page 8: ...680s at 0 5A buffer current typ 200s 400s at 1A buffer current typ 68s 136s at 3A buffer current typ 39s 78s at 5A buffer current typ 26s 53s at 7A buffer current typ 16 5s 33s at 10A buffer current...

Page 9: ...ad min 1mA at 5Vdc min permissible load Isolation voltage 500Vac signal port to power port 8 INHIBIT INPUT The inhibit input disables buffering In normal mode a static signal is required In buffer mod...

Page 10: ...Power Supply Output DC UPS Output full empty Capacitor Ready Contact closed open Buffering Contact closed open 5s 70s Example A The buffer event is longer than 1s and ends before the buffer capacitors...

Page 11: ...pacitor fully charged typ 5 0W During charging 0A output current Fig 10 1 Efficiency vs output current in normal mode typ Fig 10 2 Power losses vs output current in normal mode typ Power losses versus...

Page 12: ...10A 55 C 19 000h 34 000h 19 000h 34 000h at 24V 15A 55 C MTBF UC10 241 UC10 242 MTBF SN 29500 IEC 61709 1 519 000h 1 515 000h at 24V 10A 25 C 1 443 000h 1 439 000h at 24V 15A 25 C 899 000h 895 000h a...

Page 13: ...9 50 A Remaining capacity A 85 B 75 B 15A Output Current 12 FUNCTIONAL DIAGRAM Fig 12 1 Functional diagram 24V Power Supply Boost Converter Step up Converter Charger Balancing Safety Circuits Input E...

Page 14: ...onnecting a wire Instructions a Use appropriate copper cables that are designed for minimum operating temperatures of 60 C for ambient up to 45 C and 75 C for ambient up to 60 C and 90 C for ambient u...

Page 15: ...Flashing pattern for the red warning LED Check input voltage 1 0 1 0 PC Mode activated AUU Input Terminals quick connect spring clamp terminal UUBUU Output Terminals quick connect spring clamp termina...

Page 16: ...coupling clamp Criterions A DC UPS shows normal operation behavior within the defined limits EMC Emission According generic standards EN 61000 6 3 and EN 61000 6 4 Conducted emission IEC CISPR 16 1 2...

Page 17: ...2103 EN 50178 not conductive LABS compatibility The unit does not release any silicone or other LABS critical substances and is suitable for use in paint shops Operational temperature is the same as t...

Page 18: ...ve balancing circuit ensures uniform capacitor voltages If necessary the charging current will be reduced to a safe value Failing of one or more capacitor in the capacitor string included Ready contac...

Page 19: ...TEX certificate EPS 15 ATEX 1 025 X The power supply must be built in in an IP54 enclosure EN 60079 0 EN 60079 15 ATEX II 3G Ex nA nC II T4 Gc Suitable for use in Class 1 Zone 2 Groups IIa IIb and IIc...

Page 20: ...The DIN rail height must be added to the unit depth 127mm to calculate the total required installation depth Installation Clearances See chapter XX2XX Fig 21 1 Front view UC10 241 Fig 21 2 Front view...

Page 21: ...s bracket is used to mount the DC UPS onto a flat surface without utilizing a DIN Rail UC10 241 UC10 242 May 2016 Rev 2 2 DS UC10 241 EN All parameters are specified at 24V 10A output current 25 C amb...

Page 22: ...the wire size that is used the wiring is considered as thermally safe regardless of whether the MCB opens or not To avoid voltage dips and under voltage situations in adjacent 24V branches which are s...

Page 23: ...2 Wiring example for a fully redundant system redundant power supplies and redundant DC UPSs Power Supply 24V Output Power Supply 24V Output Load Failure Monitor YRM2 DIODE OUT IN 1 IN 2 IN 1 IN 2 23...

Page 24: ...tic signal is required In buffer mode a pulse with a minimum length of 250ms is required to stop buffering The inhibit signal is stored and can be reset by cycling the input voltage For service purpos...

Page 25: ...ontact closed External signal to start the delayed shut down Load open closed Buffering Contact open 1s full empty Capacitor Pin 7 8 open Ready Threshold 250ms Activation of the external control mode...

Page 26: ...depends on the load current the lower the load current the lower the cut off voltage Considering this voltage range the energy can be calculated with the following formula full charge voltage U1 2 5V...

Page 27: ...ee notes in section 2 first Symptom Action Check input voltage LED is on Check input voltage must be between 22 8V and 30V DC UPS did not buffer Inhibit input was set Capacitor did not have enough tim...

Reviews: