10.1 Wiring diagram 

Figure 10 shows the standard electrical connections. However, the wiring diagram inside the actuator hood 
is valid for the specific actuator. For any optional extras see the individual wiring diagram in the related 
service instructions.  
 
Two adjustable limit switches are installed to limit the stroke of the actuator, and cut-off the motor current 
in the relative direction. 

 

 

PE Earth connection on housing plate has to be connected!  

 
Figure 10: Wiring diagram 

11. Commissioning 

 

Drive the actuator into an intermediate stroke position using the hand wheel. 

 

Switch the setting signal briefly between OPEN and CLOSE and ensure that the actuator operates in the 
correct direction. If necessary, reverse the setting signal for OPEN / CLOSE. 

 

Drive the actuator, in both directions, using the setting signal until the limit switch cuts-off. Ensure that 
the limit switch position is correct. If necessary re-adjust the limit switches.  

12. Service/ Maintenance 

The actuators are maintenance-free if used under the operating conditions as stated in the data sheet. The 
gearboxes are lubricated for lifetime and do not require further lubrication. 
 

12.1 Cleaning 

The actuators should be cleaned dryly. 

230, 115, 24 VAC 1~ 

400 VAC 3~

 

24 VDC

 

 

Summary of Contents for PSQ-E Series

Page 1: ...Operating Instructions PSQ E Version 2019 01 08 2019 PS Automation GmbH...

Page 2: ...internal limit switches 8 9 2 Setting of the additional position switches 9 10 Electric supply 9 10 1 Wiring diagram 10 11 Commissioning 10 12 Service Maintenance 10 12 1 Cleaning 10 12 2 Spare Parts...

Page 3: ...ication This may cause danger to life and limb of the user or a third party damage the actuator and other property belonging to the owner reduce safety and function of the actuator To prevent such pro...

Page 4: ...ried out on the actuators are excluded from the manufacturer s liability Supply voltage may only be switched on after the proper closure of the main cover or terminal box 3 Storage For appropriate sto...

Page 5: ...r torque is transmitted via a spur gear onto the sun wheel of a Wolfrom gear The rotating output wheel of the Wolfrom gear holds a removable drive bush to connect the actuator with the valve stem Two...

Page 6: ...clutching or declutching Figure 4 Manual operation Do not exceed the adjusted electrical stroke limits by using the hand wheel The mechanical stop must be set accordingly to protect the valve If you...

Page 7: ...osed in order to avoid that components inside the actuator are damaged 8 Setting of the mechanical stop There are two adjustable screws installed for setting the mechanical limit of the angular travel...

Page 8: ...ternal limit switches Ensure that the mains supply is secured against accidental switching on The limit switches are pre adjusted in the factory An additional adjustment of the two lower switching cam...

Page 9: ...ition and repeat the adjustment if necessary 10 Electric supply Switch mains off before starting to work Connect acc to wiring diagram on the main frame The mains supply cords must be suitably dimensi...

Page 10: ...into an intermediate stroke position using the hand wheel Switch the setting signal briefly between OPEN and CLOSE and ensure that the actuator operates in the correct direction If necessary reverse t...

Page 11: ...r works in Bad Duerkheim Germany or to our representatives for evaluation of failures and repair 13 Appendix 13 1 Accessories Various options are available in order to adapt the actuators to the vario...

Page 12: ...12 13 2 Declaration of Incorporation of Part Completed Machinery and EC Declaration of Conformity in compliance with the Directives on EMC and Low Voltage...

Page 13: ...Sytc HK Super net www maxonicauto com India PS Automation India Pvt Ltd Srv No 25 1 Narhe Industrial Area A P Narhegaon Tal Haveli Dist IND 411041 Pune Phone 91 20 25 47 39 66 Fax 91 20 25 47 39 66 E...

Reviews: