Staging is controlled by the number of minutes heating or 
cooling has been calling.  The Timer monitors the continuous 
call time and forces staging when the call time exceeds the 
preset limits.

Staging can be disabled if the outdoor temperature exceeds 
the preset limits. 

Staging Based on Call Timer

Limit Staging Based on Outdoor Temperature

Press Yes to select timed upstaging.

Press Up or Down to set the number 
of minutes of continuous call time 
required to upstage to Stage2. Press 
NEXT to continue.

Press Up or Down to set the number 
of minutes of continuous call time 
required to upstage to Stage3. Press 
NEXT to continue to the next menu 
selection.

Press Yes to select limiting upstaging 
based on outdoor temperature.

Press Up or Down to set the outdoor 
temperature to disable staging 
heating.  If the outdoor temperature is 
above the limit, staging of heating is 
disabled.  Press NEXT to continue.

Press Up or Down to set the outdoor 
temperature to disable staging 
cooling.  If the outdoor temperature is 
below the limit, staging of cooling is 
disabled.  Press NEXT to continue to 
the next menu selection.

Timed
UpStaging    Y/N

Stage 2       20
Minutes U/D/NEXT

Stage 3       30
Minutes U/D/NEXT

Limit Staging
OD Temp      Y/N

OD Temp Lmt   60
Heating U/D/NEXT

OD Temp Lmt   55
Cooling U/D/NEXT

A damper can be used to bring outdoor air into the return to 
maintain a healthy home.  The equipment fan draws in the 
outdoor air and mixes it with the return air from the home. 
The panel attemps to fulfill the required fresh air during 
heating and cooling calls. As the end of each hour 
approaches, the panel will open the fresh air damper and 
activate the indoor fan (G) if additional fresh air minutes are 
required.  

The PDMi3 allows the installer to directly set the minutes 
per hour the fresh air damper is open or the PDMi3 can 
calculate the required CFM of fresh air based on the area 
of the home and the number of bedrooms. 

Fresh Air Control for Title24 and ASHRAE 62.2

Change or Set Fresh Air Operation

Press Yes to change the Fresh Air 
Option.  Press no to continue to 
another option.

Press Yes to turn the Fresh Air 
Option On or No to turn it Off.

Change Fresh Air
Option       Y/N

Fresh Air    Off
      Y-On/N-Off

If the contractor has calculated the CFM for fresh air and sized 
the damper to operate for a number of minutes each hour, the 
minutes can be directly entered.

The PDMi3 allows the installer to calculate the required CFM of 
fresh air based on the area of the home and the number of 
bedrooms.  The calculated CFM is the CFM required if the fresh 
air damper is continuously open and the indoor fan operating to 
draw in fresh air.  

The PDMi3 tutors the installer to set the area of the home in 
square feet and the number of bedrooms.  It then calculates and 
displays the minimum amount of outdoor air required to meet the 
requirement for the home.  This is the amount required if the 
indoor fan was running continuously.

If the fresh air intake is increased, the fresh air operation can 
occur mostly during calls to minimize dis-comfort.  The PDMi3 will 
then display the number of minutes of fresh air operation required 
each hour based on the minimum CFM and the selected CFM.

Direct Entry of Minutes per Hour of Fresh Air

PDMi3 Calculates Minutes per Hour of Fresh Air

Press Up or Down to set the area of 
the home.  Press NEXT to continue.

Press Yes to have the PDMi3 calculate 
the fresh air requirements.  Press No to 
directly set the minutes per hour of fresh 
air operation.continue.

Press Up or Down to set the 
number of minutes the fresh air 
damper and indoor fan must 
operate each hour to meet the fresh 
air requirements.  Press NEXT to 
continue.

Press Yes to enter the minutes of 
fresh air operation required each 
hour.  Press No to select calculating 
the CFM and minutes per hour.

Press Up or Down to set the 
bedrooms in the home.  Press NEXT 
to continue.

The PDMi3 shows the minimum CFM 
required when the fresh air duct is 
operating continuously.  

Press Up or Down to adjust the fresh 
air CFM.  Increasing the CFM to 210 
would lower the number of minutes 
per hour of fresh air operation 
allowing it to be accomplished during 
calls.  Press NEXT to continue.

The PDMi3 shows the number of 
minutes of fresh air operation each 
hour.  Press Up or Down to adjust the 
fresh air minutes each hour.  Press 
NEXT to continue to the next menu 
selection.

Fresh Air   Calc
             Y/N

Fresh Air  Enter
Min/Hr       Y/N

Area        2200
SqFt    U/D/NEXT

Bedrooms       4
        U/D/NEXT

Fresh Air     70
CFM     U/D/NEXT

Fresh Air     20
Min/Hr  U/D/NEXT

Fresh Air     20
Min/Hr  U/D/NEXT

Fresh Air    210
CFM     U/D/NEXT

Summary of Contents for ProC232J

Page 1: ...umps Selected using the PDMi3 plug in programming display module See table below See table below See table below HVAC PANEL ZONE DAMPERS 1 1 2 2 3 Fresh Air 3 THERMOSTATS Quick View Zoning Panel ProZo...

Page 2: ...the plenum or freezing the indoor coil Color coded terminals for heat cool or heat pump thermostat Thermostat type selected using the PDMi3 Use 24VAC powered or battery powered thermostats VAC termina...

Page 3: ...stall the 24VAC transformer according to local electrical codes and connect the 24VAC output to the terminals on the panel using 2 conductor 18 gage thermostat wire as shown below 1 2 3 4 HVAC PANEL Z...

Page 4: ...heat pump thermostat should be used in Zone1 when heat pump equipment is selected Wiring of a heat pump zone thermostat is shown below Thermostat R C OB W2 E Y1 G Zoning Panel Terminal Function 24VAC...

Page 5: ...the red and white thermostat wires to the thermistor wires no polarity using the wirenuts 3 Push the wirenuts and wire into the cover and secure the cover with the screw 1 Connect the red and white th...

Page 6: ...respond to the Zone1 thermostat When the occupant leaves the home they can set the switch to Vacant and only set the Zone1 thermostat Installing the Duct Pressure Sensor Drill a 3 8 inch diameter hol...

Page 7: ...es or navigate Press the CANCEL to cancel settings and return to the main menu The panel is ready to operate and control the equipment selected The PDMi3 can be used to customize the panel clone it fr...

Page 8: ...s Yes to set the number of stages of heating and cooling the fan operation the supply air temperature limits outdoor changeover temperature for dual fuel heat pumps and number of zones being used Pres...

Page 9: ...T Aux Heating 1 Stages U D NEXT Fan Mode Gas N NEXT Htg Temp Lmt 160 U D NEXT Htg Temp Lmt 160 U D NEXT Clg Temp Lmt 45 U D NEXT Clg Temp Lmt 45 U D NEXT Total Zones 3 Used U D NEXT Total Zones 3 Used...

Page 10: ...heat cool thermostat for that zone Press No to see other thermostats that can be used in that zone Press Up or Down to change the number of auxiliary heating stages Press NEXT to continue If a heat pu...

Page 11: ...Y N Bypass Ext Baro Y N Bypass ZoneDmprs Y N Zone1 Htg 50 BP Pos U D NEXT Zone1 Clg 50 BP Pos U D NEXT Zone2 Htg 50 BP Pos U D NEXT Zone2 Clg 50 BP Pos U D NEXT Zone3 Htg 50 BP Pos U D NEXT Zone3 Clg...

Page 12: ...N Fresh Air Off Y On N Off If the contractor has calculated the CFM for fresh air and sized the damper to operate for a number of minutes each hour the minutes can be directly entered The PDMi3 allows...

Page 13: ...Down to set the weighted zones when low speed fan is activated In the example if the weighted demand is less than 2 0 DSBK is activated Press Next to continue to next menu selection Press Yes to selec...

Page 14: ...ooling stage Press Yes to start a test of the heating system to insure discharge temperature is correct Press Next to start a test stage2 heating to insure discharge temperature is correct or return t...

Page 15: ...select the letter or number Press NEXT to go to the next letter in the name Press SAVE to save the clone name Monitor HVAC Performance Y N LAT 122 Prs 0 55 BP Pos 35 NEXT Press Yes to display the leav...

Page 16: ...una Hills CA 92653 949 916 0945 Fax 949 458 8502 www ProZone US com Limited 5 Year Warranty The 5 year warranty is limited to the repair or replacement of defective product due to parts failure or def...

Reviews: