Prostat SureTest PGT-61-164 Operation Manual Download Page 9

 

 

PGT-61-164 SureTest Circuit Analyzer

 

8

 
 

ASCC

1

 = Line Voltage (V

HN

)/ (Hot 

 + Neu 

)   

 

ASCC

2

 = Line Voltage (V

HN

)/ (Hot 

 + 1/(1/ Neu 

 + 1/Grd 

)  

 

Impedance (Z) Measurements 

If the voltage drop measurement exceeds 5%, analyze the hot and neutral impedances. If one is 
significantly higher than the other, the problem is with the conductor with the much higher 
impedance. Then, check all connections on that conductor back to the panel. If both impedance 
appear high, the source can be undersized wire for the length of run, a bad device, or poor 
connections at the pigtails, devices, or panel. 
 
The ground impedance measured should be less than 1 ohm as a rule of thumb to ensure that 
fault current has a sufficient path back to the panel. IEEE states the ground impedance should 
be less than 0.25 ohms to ensure the ground conductor can safely return any fault current which 
could damage equipment on the circuit. Surge suppression systems require a good ground to 
adequately protect equipment from transient overvoltages. Note that a small amount of current 
is applied to the ground conductor to accurately measure its impedance. By the inherent nature 
of this test, a GFCI protected circuit will trip unless the device is temporarily removed from the 
circuit. 
 
Troubleshooting Tips – Impedances 

Measurement 

Expected 

Result 

Problem 

Possible 

Causes 

Possible 

Solutions 

<0.48

/foot of 

14 AWG wire 

Too much load 
on branch circuit 

Redistribute the 
load on the 
circuit 

<0.03

/foot of 

12 AWG wire 

Undersized wire 
for length of run 

Check code 
requirements 
and rewire if 
necessary 

 
 
Hot and Neutral 
Impedance 

<0.01

/foot of 

10 AWG wire 

 
 
High Conductor 
impedance 

High resistance 
connection within 
the circuit or at 
the panel 

Locate high 
resistance 
connection/ 
device and 
repair/replace 

< 1

 to protect 

people 

Undersized wire 
for length of run 

Check code 
requirements 
and re-wire if 
necessary 

 
Ground 
Impedance 

<0.25

 to 

protect 
equipment 

 
High ground 
impedance 

High resistance 
connection within 
the circuit or at 
the panel 

Locate high 
resistance 
connection/ 
device and 
repair/replace 

 
 
 
 

 

Summary of Contents for SureTest PGT-61-164

Page 1: ...P R O F E S S I O N A L S T A T I C C O N T R O L P R O D U C T S Operations Manual SureTest Universal Circuit Analyzer PGT 61 164 SureTest Manufactured by Ideal Industries Sycamore Illinois USA...

Page 2: ...n the United States of America No part of this manual may be used or reproduced in any manner whatsoever without written permission For information contact PROSTAT Corporation 1072 Tower Lane Bensenvi...

Page 3: ...lyzer 2 TABLE OF CONTENTS PROSTAT PGT 61 164 SURETEST CIRCUIT ANALYZER Title Page I Introduction 3 II General Operation 3 III Menu Navigation 4 IV GFCI Test Button 5 V Testing Procedure 5 VI GFCI Test...

Page 4: ...Frequency Measures Hot Neutral and Ground conductor impedances Identifies proper wiring in 3 wire receptacles Identifies false bootleg grounds Tests GFCI s for proper operation Includes 1 ft extension...

Page 5: ...nu displays the True RMS line voltage in real time This main menu has a sub menu positioned horizontally at the bottom of the screen that displays the line voltage RMS HN ground to ground voltage RMS...

Page 6: ...lse Ground If the wiring condition is other than normal the SureTest is limited on its measurements that can be performed If a no ground condition exists only the line voltage and voltage drop measure...

Page 7: ...ute loads on the circuit High Resistance connection within the circuit or at the panel Locate high resistance connection device and repair replace Line Voltage 120 VAC 220 VAC 108 132 VAC 198 242 VAC...

Page 8: ...e run or too much current on the circuit Check the wire to ensure that it is sized per sode and measure the current on the branch circuit If a voltage drop reading changes significantly from one recep...

Page 9: ...ood ground to adequately protect equipment from transient overvoltages Note that a small amount of current is applied to the ground conductor to accurately measure its impedance By the inherent nature...

Page 10: ...test a GFCI in a 2 wire system no ground the 61 175 ground continuity adapter sold separately must be used Connect the alligator clip on the adapter to a ground source such as to a metal water or gas...

Page 11: ...ime GFCI maybe installed improperly Check wiring for proper installation in accordance with manufacturer s instructions and NEC GFCI Test GFCI trips within trip time GFCI doesn t trip GFCI may be defe...

Page 12: ...Instrument has been evaluated and complies with insulation category III Overvoltage category III Pollution degree 2 in accordance with IEC 644 Indoor use Measurement Specifications All specifications...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...Copyright 2001 2007 Prostat Corporation Printed in U S A 1072 Tower Lane Bensenville IL 60106 USA www prostatcorp com...

Reviews: