Prostat SureTest PGT-61-164 Operation Manual Download Page 6

 
 

PGT-61-164 SureTest Circuit Analyzer 

5

 
 

IV. 

GFCI Test Button 

 

Depressing this button displays the GFCI main menu. Two 
tests can be performed in this menu: 

GFCI

 and 

EPD

. The 

GFCI tests 

G

round 

F

ault 

C

ircuit 

I

nterrupting devices by 

faulting 6-9mA from hot-to-ground per UL-1436. The 

EPD

 tests those breakers, which 

have an 

E

quipment 

P

rotective 

D

evice feature that trips the breaker if a ground fault of 

greater than 30mA is detected. Pressing the side arrow button ( 

 ) navigates between 

these two sets. Once the desired test is highlighted, depress the GFCI test button on the 
keypad to activate the test. 

 

V. Testing 

Procedure 

 

Wiring Verification 

Immediately after being inserted into a receptacle, the SureTest 
displays the IDEAL logo while it performs a battery of tests. The 
first test result displayed is the wiring condition. The SureTest 
checks for the following conditions and indicates the test result on 
the display. 
 

Wiring Condition 

 

Display Indication 

 

 

 

 

 
Correct Wiring 

 

 

 

 

 

No Ground 

 

 

 

 

 

Polarity Reversal

 

 

 

 

 

Open/Hot Neutral

 

 

 

 

 

False Ground

  

 

 

 
If the wiring condition is other than normal, the SureTest is limited on its measurements that can 
be performed. If a no ground condition exists, only the line voltage and voltage drop 
measurement are available. In a hot/ground reversal, open neutral or open hot condition, the 
unit will not have any power so the display will be blank. 
 

Notes:

 

1)  Will not detect two hot wires in a circuit. 
2)  Will not detect a combination of defects. 
3)  Will not detect reversal of grounded and grounding conductors. 

 
False Ground Indication 

NEC article 250-23(a) only allows for a neutral to ground bond to occur at the main panel. The 
SureTest suggests any improper neutral-to-ground bonds within 15-20 feet upstream (towards 
the panel) of the tester. If this bond improperly occurs in the branch circuit through a bootleg 
ground via a jumper wire at the outlet device or inadvertent contact of the ground wire to the 
neutral connection, the SureTest indicates a false ground condition. Note that if the SureTest is 
within 15-20 feet of the main panel, the unit will indicate a false ground condition on a properly 
wired circuit due to its close proximity to the proper ground-neutral bond in the main panel. 

Legend 
 
  

 On 

  

 Off 

  

 Flashing 

Summary of Contents for SureTest PGT-61-164

Page 1: ...P R O F E S S I O N A L S T A T I C C O N T R O L P R O D U C T S Operations Manual SureTest Universal Circuit Analyzer PGT 61 164 SureTest Manufactured by Ideal Industries Sycamore Illinois USA...

Page 2: ...n the United States of America No part of this manual may be used or reproduced in any manner whatsoever without written permission For information contact PROSTAT Corporation 1072 Tower Lane Bensenvi...

Page 3: ...lyzer 2 TABLE OF CONTENTS PROSTAT PGT 61 164 SURETEST CIRCUIT ANALYZER Title Page I Introduction 3 II General Operation 3 III Menu Navigation 4 IV GFCI Test Button 5 V Testing Procedure 5 VI GFCI Test...

Page 4: ...Frequency Measures Hot Neutral and Ground conductor impedances Identifies proper wiring in 3 wire receptacles Identifies false bootleg grounds Tests GFCI s for proper operation Includes 1 ft extension...

Page 5: ...nu displays the True RMS line voltage in real time This main menu has a sub menu positioned horizontally at the bottom of the screen that displays the line voltage RMS HN ground to ground voltage RMS...

Page 6: ...lse Ground If the wiring condition is other than normal the SureTest is limited on its measurements that can be performed If a no ground condition exists only the line voltage and voltage drop measure...

Page 7: ...ute loads on the circuit High Resistance connection within the circuit or at the panel Locate high resistance connection device and repair replace Line Voltage 120 VAC 220 VAC 108 132 VAC 198 242 VAC...

Page 8: ...e run or too much current on the circuit Check the wire to ensure that it is sized per sode and measure the current on the branch circuit If a voltage drop reading changes significantly from one recep...

Page 9: ...ood ground to adequately protect equipment from transient overvoltages Note that a small amount of current is applied to the ground conductor to accurately measure its impedance By the inherent nature...

Page 10: ...test a GFCI in a 2 wire system no ground the 61 175 ground continuity adapter sold separately must be used Connect the alligator clip on the adapter to a ground source such as to a metal water or gas...

Page 11: ...ime GFCI maybe installed improperly Check wiring for proper installation in accordance with manufacturer s instructions and NEC GFCI Test GFCI trips within trip time GFCI doesn t trip GFCI may be defe...

Page 12: ...Instrument has been evaluated and complies with insulation category III Overvoltage category III Pollution degree 2 in accordance with IEC 644 Indoor use Measurement Specifications All specifications...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...Copyright 2001 2007 Prostat Corporation Printed in U S A 1072 Tower Lane Bensenville IL 60106 USA www prostatcorp com...

Reviews: