I. Introduction 

 

 

 

Utilizing patented technology, the SureTest circuit analyzer “look behind walls” to identify 

wiring problems that can lead to personal shock hazards, electrical fires, or equipment 
performance issues. Personal shock hazards stem from poor grounding, false grounds, 
and/or no ground fault protection. Electrical fires are primarily caused from arc faults 
and high resistance points that lead to glowing connections in the circuit wiring. And, 
equipment performance issues arise due to insufficient voltage available under load, 
poor impedance, and high ground-to-neutral voltage. In fact, it’s estimated that 80% of 
power quality performance issues are related to the faulty wiring issues stated above. 

 
 

Product Features 

• 

True RMS 

• 

Measures voltage drop under 12, 15 and 20-amp loads 

• 

Measures voltage: Line, Ground-to-Neutral, Peak, Frequency 

• 

Measures Hot, Neutral and Ground conductor impedances 

• 

Identifies proper wiring in 3-wire receptacles 

• 

Identifies false (bootleg) grounds 

• 

Tests GFCI’s for proper operation 

• 

Includes 1-ft extension cord 

 

II. General 

Operation 

 

The PGT-61-164 SureTest Circuit Analyzer takes only seconds to test each outlet and 
circuit under a full load. This test tool checks for various wiring conditions including: 
correct wiring, polarity reversal and no ground per UL-1436. A simple menu gives access 
to measurements of line voltage, voltage drop under a full load condition, ground-neutral 
voltage and line impedances. The ground fault circuit interrupter (GFCI) test is performed 
separately, in accordance with UL-1436 and will disrupt the electrical supply if a 
functional GFCI is present. 
 

 

 
 
 
 
 
 
 
 
 
 

WARNING!  

Do not use on outputs from UPS system, light dimmers or square 

wave generating equipment, as damage to the analyzer will occur. 

WARNING!  

To maintain stated accuracies during repeated use, allow 20 

seconds between insertions to adequately dissipate any heat 

buildup during the load testing. 

Summary of Contents for SureTest PGT-61-164

Page 1: ...P R O F E S S I O N A L S T A T I C C O N T R O L P R O D U C T S Operations Manual SureTest Universal Circuit Analyzer PGT 61 164 SureTest Manufactured by Ideal Industries Sycamore Illinois USA...

Page 2: ...n the United States of America No part of this manual may be used or reproduced in any manner whatsoever without written permission For information contact PROSTAT Corporation 1072 Tower Lane Bensenvi...

Page 3: ...lyzer 2 TABLE OF CONTENTS PROSTAT PGT 61 164 SURETEST CIRCUIT ANALYZER Title Page I Introduction 3 II General Operation 3 III Menu Navigation 4 IV GFCI Test Button 5 V Testing Procedure 5 VI GFCI Test...

Page 4: ...Frequency Measures Hot Neutral and Ground conductor impedances Identifies proper wiring in 3 wire receptacles Identifies false bootleg grounds Tests GFCI s for proper operation Includes 1 ft extension...

Page 5: ...nu displays the True RMS line voltage in real time This main menu has a sub menu positioned horizontally at the bottom of the screen that displays the line voltage RMS HN ground to ground voltage RMS...

Page 6: ...lse Ground If the wiring condition is other than normal the SureTest is limited on its measurements that can be performed If a no ground condition exists only the line voltage and voltage drop measure...

Page 7: ...ute loads on the circuit High Resistance connection within the circuit or at the panel Locate high resistance connection device and repair replace Line Voltage 120 VAC 220 VAC 108 132 VAC 198 242 VAC...

Page 8: ...e run or too much current on the circuit Check the wire to ensure that it is sized per sode and measure the current on the branch circuit If a voltage drop reading changes significantly from one recep...

Page 9: ...ood ground to adequately protect equipment from transient overvoltages Note that a small amount of current is applied to the ground conductor to accurately measure its impedance By the inherent nature...

Page 10: ...test a GFCI in a 2 wire system no ground the 61 175 ground continuity adapter sold separately must be used Connect the alligator clip on the adapter to a ground source such as to a metal water or gas...

Page 11: ...ime GFCI maybe installed improperly Check wiring for proper installation in accordance with manufacturer s instructions and NEC GFCI Test GFCI trips within trip time GFCI doesn t trip GFCI may be defe...

Page 12: ...Instrument has been evaluated and complies with insulation category III Overvoltage category III Pollution degree 2 in accordance with IEC 644 Indoor use Measurement Specifications All specifications...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...Copyright 2001 2007 Prostat Corporation Printed in U S A 1072 Tower Lane Bensenville IL 60106 USA www prostatcorp com...

Reviews: