PGT-61-164 SureTest Circuit Analyzer
11
PGT-61-164 SureTest
®
Circuit Analyzer Specifications
General Specifications
Display: 128x64
OLED
with
backlight
Display update for Volt:
Less than 2.5 times second
Over-range indication on all functions:
Display “OL”
Operating Environment,
Relative Humidity:
32
o
F to 122
o
F (0
o
C to 50
o
C) at <80% Rh
Storage Environment:
32
o
F to 122
o
F (0
o
C to 50
o
C) at <80% Rh
Case Construction:
ABS UL 94 V/0/5VA Rated
Altitude: 6561.7
ft.
(2000m)
Dimensions:
6.4” (L) x 3” (W) x 1.4” (D)
162mm (L) x 76mm (W) x 36mm (D)
Weight:
9.4 oz (267 g)
Safety:
UL61010B-1,
Cat
III-300V
UL-1436 for AFCI, GFCI & Outlet
Accessories:
Includes 1’ plug adapter and instruction manual
Double Insulation
Instrument has been evaluated and complies with insulation category III, (Overvoltage category
III) Pollution degree 2 in accordance with IEC-644. Indoor use.
Measurement Specifications
All specifications are at 23
o
C +/- 5
o
C at less than 80% relative humidity
Accuracy is stated as +/- ((% of range) + (counts))
AC converter is true rms sensing
Measurement Ranges
Resolution
Accuracy
Line Voltage
85.0 – 250.0 VAC
0.1 V
1.0% ± .2 V
Peak Line Voltage
121.0 – 354.0 VAC
0.1 V
1.0% ± .2 V
Frequency
45.0 – 65.0 Hz
0.1 Hz
1.0% ± .2 V
% Voltage Drop
0.1% - 99.9 %
0.1 %
2.5% ± .2 %
Voltage Loaded
10.0 – 250.0 VAC
0.1 V
2.5% ± .2 %
Neutral-Ground V
0.0 – 10.0 VAC
0.1 V
2.5% ± .2 %
Impedance – Hot
Neutral, & Ground
0.0
Ω
- 3.00
Ω
1.0 > 3
Ω
0.01
Ω
2.5% ± .02
Ω
Unspecified
GFCI Trip Time
1mS to 6.500S
counter
1 mS
1.0% ± .2mS
GFCI Trip Current
6.0 – 9.0 mA
0.1 mA
1.0% ± .2 mA
EPD Trip Current
30.0 – 37.0 mA
0.1 mA
1.0% ± .2 mA
Rev: PGT-61-164 – 06-2005
Format modification: 01-20-2005