Prostat SureTest PGT-61-164 Operation Manual Download Page 7

 

 

PGT-61-164 SureTest Circuit Analyzer

 

6

 
 

Voltage Measurements 

The line voltage measurement should be 120 VAC +/-10% fluctuation at 60 Hz. The peak 
voltage should be 1.414 times the rms line voltage reading for a clean sine waveform. Ground-
to-neutral voltage should be less than 2 VAC. In a single-phase circuit, a higher ground-neutral 
voltage indicates excessive current leakage between the neutral and ground conductors. In a 3-
phase circuit with a shared neutral, a high ground-neutral voltage could indicate an unbalanced 
load between the three phases or harmonic distortion on the shared neutral. Excessive ground-
neutral voltage may result in inconsistent or intermittent equipment performance. 
Troubleshooting Tips for Voltage Issues 
 
 

 
 

 

Measurement 

Expected 

Result 

Problem Possible 

Causes 

Possible 

Solutions 

Too much load on 
the load on circuit 

Redistribute loads 
on the circuit 

High Resistance 
connection within the 
circuit or at the panel 

Locate high 
resistance 
connection/ device 
and repair/replace 

 
 
Line Voltage 
120 VAC 
220 VAC 

 
 
 
108-132 VAC 
198-242 VAC 

 
 
 
High/low 

Supply voltage too 
high/low 

Consult Power 
company 

Current leaking from 
neutral to ground 

Idenify source of 
leakage; multiple 
bonding points, 
equipment or 
devices 

Unbalanced 3-phase 
system 

Check load 
balance and 
redistribute load 

 
 
Neutral-Ground 
Voltage 

 
 
< 2 VAC 
Voltage 

 
 
High G-N 
>2 VAC 

Triplen harmonics 
returning on neutral 
in 3-phase system 

Oversize neutral to 
impedance. 
Reduce harmonic 
effect via filter or 
other methods 

Supply voltage 
Too high/low 

Consult power 
company 

Peak Voltage 
120 VAC 
220 VAC 

 
153-185 VAC 
280-342 VAC 

 
High/Low 
Peak voltage 

High Peak Loads on 
line caused by 
electronic equipment 
on line 

Evaluate number 
of electronic 
devices on circuit 
and redistribute if 
necessary 

Frequency 60 

HZ  High/Low 

Frequency 

Supply frequency 
Too high/low 

Consult power 
Company 

 

 

WARNING!  

Do not exceed the unit’s maximum voltage rating of 250VAC! 

Summary of Contents for SureTest PGT-61-164

Page 1: ...P R O F E S S I O N A L S T A T I C C O N T R O L P R O D U C T S Operations Manual SureTest Universal Circuit Analyzer PGT 61 164 SureTest Manufactured by Ideal Industries Sycamore Illinois USA...

Page 2: ...n the United States of America No part of this manual may be used or reproduced in any manner whatsoever without written permission For information contact PROSTAT Corporation 1072 Tower Lane Bensenvi...

Page 3: ...lyzer 2 TABLE OF CONTENTS PROSTAT PGT 61 164 SURETEST CIRCUIT ANALYZER Title Page I Introduction 3 II General Operation 3 III Menu Navigation 4 IV GFCI Test Button 5 V Testing Procedure 5 VI GFCI Test...

Page 4: ...Frequency Measures Hot Neutral and Ground conductor impedances Identifies proper wiring in 3 wire receptacles Identifies false bootleg grounds Tests GFCI s for proper operation Includes 1 ft extension...

Page 5: ...nu displays the True RMS line voltage in real time This main menu has a sub menu positioned horizontally at the bottom of the screen that displays the line voltage RMS HN ground to ground voltage RMS...

Page 6: ...lse Ground If the wiring condition is other than normal the SureTest is limited on its measurements that can be performed If a no ground condition exists only the line voltage and voltage drop measure...

Page 7: ...ute loads on the circuit High Resistance connection within the circuit or at the panel Locate high resistance connection device and repair replace Line Voltage 120 VAC 220 VAC 108 132 VAC 198 242 VAC...

Page 8: ...e run or too much current on the circuit Check the wire to ensure that it is sized per sode and measure the current on the branch circuit If a voltage drop reading changes significantly from one recep...

Page 9: ...ood ground to adequately protect equipment from transient overvoltages Note that a small amount of current is applied to the ground conductor to accurately measure its impedance By the inherent nature...

Page 10: ...test a GFCI in a 2 wire system no ground the 61 175 ground continuity adapter sold separately must be used Connect the alligator clip on the adapter to a ground source such as to a metal water or gas...

Page 11: ...ime GFCI maybe installed improperly Check wiring for proper installation in accordance with manufacturer s instructions and NEC GFCI Test GFCI trips within trip time GFCI doesn t trip GFCI may be defe...

Page 12: ...Instrument has been evaluated and complies with insulation category III Overvoltage category III Pollution degree 2 in accordance with IEC 644 Indoor use Measurement Specifications All specifications...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...Copyright 2001 2007 Prostat Corporation Printed in U S A 1072 Tower Lane Bensenville IL 60106 USA www prostatcorp com...

Reviews: