Prostat SureTest PGT-61-164 Operation Manual Download Page 8

 
 

PGT-61-164 SureTest Circuit Analyzer 

7

 
 
Voltage Drop (V

D

) Measurements

 

The SureTest measures the line voltage, applies a load on the circuit, measures the loaded 
voltage, then calculates the voltage drop. Results are displayed for 12A, 15A, and 20A loads. 
The National Electrical Code recommends 5% as the maximum voltage drop for branch circuits 
for reasonable efficiency (NEC article 210-19, FPN 4). And, the voltage under load (V

L

) should 

not drop below 108VAC for reliable equipment operation. 
 
A good branch circuit should start out with less than 5% voltage drop at the furthest receptacle 
from the panel at the end of the cable run. Then, each receptacle tested in sequence towards 
the panel should show a steady decrease in voltage drop. If the voltage drop is above 5% and 
does not noticeably decrease, as you get closer to the first device on the circuit, then the 
problem is between the device and the panel, and the circuit breaker connections. High 
resistance points can usually be identified as hot spots using an infrared thermometer or by 
measuring the voltage across the breaker. If the voltage drop exceeds 5% but noticeably 
decreases as you nearer the panel, the circuit may have undersized wire, too long of a cable 
run, or too much current on the circuit. Check the wire to ensure that it is sized per sode and 
measure the current on the branch circuit. If a voltage drop reading changes significantly from 
one receptacle to the next, then the problem is a high impedance point at or between two 
receptacles. It is usually located at a termination point, such as a bad splice or loose wire 
connection, but it might also be a bad receptacle. 
 
Troubleshooting Tips for Voltage Drop 
 

Measurement 

Expected 

Result 

Problem 

Possible 

Causes 

Possible 

Solutions 

Too much load 
on the circuit 

Redistribute the 
load on the 
circuit 

Undersized wire 
for length of run 

Check code 
requirement and 
re-wire if 
necessary 

 
Voltage Drop 

 
<5% 

 
High Voltage 
Drop 

High resistance 
connection within 
the circuit or al 
the panel 

Locate high 
resistance 
connection/ 
device and 
repair/replace 

 
 

ASCC Measurement 

The SureTest calculates the Available Short-Circuit Current (ASCC) that the branch circuit can 
deliver through the breaker during a bolted fault (dead-short) condition. 
 
The ASCC is calculated by dividing the line voltage by the circuit’s line impedance (hot + 
neutral). Depressing the side arrow (

) displays the worst-case scenario where all three 

conductors (hot, neutral, ground) are shorted together – the neutral and ground provide a lower 
impedance via a parallel return path. Note that this second test will trip a GFCI. See the 
following equations for clarification. 
 

Summary of Contents for SureTest PGT-61-164

Page 1: ...P R O F E S S I O N A L S T A T I C C O N T R O L P R O D U C T S Operations Manual SureTest Universal Circuit Analyzer PGT 61 164 SureTest Manufactured by Ideal Industries Sycamore Illinois USA...

Page 2: ...n the United States of America No part of this manual may be used or reproduced in any manner whatsoever without written permission For information contact PROSTAT Corporation 1072 Tower Lane Bensenvi...

Page 3: ...lyzer 2 TABLE OF CONTENTS PROSTAT PGT 61 164 SURETEST CIRCUIT ANALYZER Title Page I Introduction 3 II General Operation 3 III Menu Navigation 4 IV GFCI Test Button 5 V Testing Procedure 5 VI GFCI Test...

Page 4: ...Frequency Measures Hot Neutral and Ground conductor impedances Identifies proper wiring in 3 wire receptacles Identifies false bootleg grounds Tests GFCI s for proper operation Includes 1 ft extension...

Page 5: ...nu displays the True RMS line voltage in real time This main menu has a sub menu positioned horizontally at the bottom of the screen that displays the line voltage RMS HN ground to ground voltage RMS...

Page 6: ...lse Ground If the wiring condition is other than normal the SureTest is limited on its measurements that can be performed If a no ground condition exists only the line voltage and voltage drop measure...

Page 7: ...ute loads on the circuit High Resistance connection within the circuit or at the panel Locate high resistance connection device and repair replace Line Voltage 120 VAC 220 VAC 108 132 VAC 198 242 VAC...

Page 8: ...e run or too much current on the circuit Check the wire to ensure that it is sized per sode and measure the current on the branch circuit If a voltage drop reading changes significantly from one recep...

Page 9: ...ood ground to adequately protect equipment from transient overvoltages Note that a small amount of current is applied to the ground conductor to accurately measure its impedance By the inherent nature...

Page 10: ...test a GFCI in a 2 wire system no ground the 61 175 ground continuity adapter sold separately must be used Connect the alligator clip on the adapter to a ground source such as to a metal water or gas...

Page 11: ...ime GFCI maybe installed improperly Check wiring for proper installation in accordance with manufacturer s instructions and NEC GFCI Test GFCI trips within trip time GFCI doesn t trip GFCI may be defe...

Page 12: ...Instrument has been evaluated and complies with insulation category III Overvoltage category III Pollution degree 2 in accordance with IEC 644 Indoor use Measurement Specifications All specifications...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...Copyright 2001 2007 Prostat Corporation Printed in U S A 1072 Tower Lane Bensenville IL 60106 USA www prostatcorp com...

Reviews: