The following table defines the values and their associated operations:
Swap Code
Description
0
None: No Change is made in the byte ordering (1234 = 1234)
1
Words: The words are swapped (1234=3412)
2
Words & Bytes: The words are swapped then the bytes in each word are
swapped (1234=4321)
3
Bytes: The bytes in each word are swapped (1234=2143)
Delay Preset
0 to 65535 milliseconds
This parameter controls how often this command will copy data between different
areas in the database. Set the Delay Preset for different intervals for each row in
the [Data Map] section.
If multiple copy operations (several rows in the [Data Map] section) happen at the
same time, they could delay the process scan of the gateway protocols. For
example, you should not set all values to a delay preset of 1000. Instead, use
values such as 1000, 1001 and 1002, or any other delay different delay preset
values you like. This will prevent the copies from happening concurrently and
prevent possible process scan delay.