Reference S3964R
♦
ProLinx Gateway
Driver Manual
Siemens 3964R Protocol
ProSoft Technology, Inc.
Page 53 of 64
April 14, 2009
6.2.2 Error
Codes
Error Code
Description
-1
0xFFFF
Multi-block timeout error.
-2
0xFFFE
DLE could not be sent
-10
0xFFF6
DLE not received in time
-11
0xFFF5
Communication Timeout occurred
-20
0xFFEC
Invalid character or acknowledge received
-30
0xFFE2
Amount of user data is 0 or greater than 256 words
-31
0xFFE1
Reject pending job from the Modbus TCP/IP device due to low priority
-32
0xFFE0
No reaction (STX) from Communication Partner
-33 0xFFDF
Communication
Partner error occurred
-34
0xFFDE
Job code not defined
-35
0xFFDD
High/High (priority) initialization conflict occurred
-36
0xFFDC
First Header Byte does not match telegram type
-37
0xFFDB
Character received was not an STX
-38 0xFFDA
S3964R problem occurred after connection to Communication Partner was
established
-39
0xFFD9
S3964R communication could not be established/finished
-97 0xFF9F
Unable to write message data received from the 3964R Communication
Partner to the database because the last data written to the database has not
been read yet. When data has been read from the database, the Modbus
TCP/IP device must update the "Last Receive Block Number" in the transmit
buffer to be equal to the “Sequence Number” in the receive buffer.
-98
0xFF9E
Multi-block transfer timeout
-99
0xFF9D
Pass-through transfer failed