3.1.3 Functional Specifications - DNP 3.0 Slave
The DNP 3.0 Slave driver provides extensive support for Slave implementations
of the protocol. The serial port on the gateway is user-configurable to support the
DNP 3.0 protocol (Slave, Error Checking, Baud rate, and so on).
General Parameters
Internal Database
Binary Inputs: 0 to 500 word count
Analog Inputs: 0 to 500 points
Counters: 0 to 250 points
Binary Outputs: 0 to 200 word count
Analog Outputs: 0 to 500 points
Binary Input Events: 0 to 100 event buffer
Analog Input Events: 0 to 100 event buffer
Communication parameters
Baud Rate: 110 to 115K baud
Stop Bits: 1
Data Size: 8 bits
Parity: None
RTS Timing delays: 0 to 65535 milliseconds
DNP Mode
DNP 3.0 Slave - Level 2
DNP Slave
Node address
0 to 65534 (software selectable)
3.1.4 Hardware
Specifications
Specification Description
Power Supply
24 VDC nominal
18 to 32 VDC allowed
Positive, Negative, GND Terminals
2.5 mm screwdriver blade
Current Load
500 mA max@ 32 VDC max
Operating Temperature
-20 to 50°C (-4 to 122°F)
Storage Temperature
-40 to 85°C (-40 to 185°F)
Relative Humidity
5% to 95% (non-condensing)
Dimensions
Standard: 5.20 H x 2.07 W x 4.52 D inches
(13.2 cm H x 5.25 cm W x 11.48cm D)
Extended: 5.20 H x 2.73 W x 4.52 D inches
(13.2 cm H x 6.934 cm W x 11.48cm D)
LED Indicators
Power and Module Status
Application Status
Serial Port Activity LED
Serial Activity and Error LED Status
Configuration
Serial Port
DB-9M RS-232 only
No hardware handshaking