ProLinx DNPS
♦
ProLinx Gateway
Start Here
DNP 3.0 Slave
User Manual
Page 18 of 86
ProSoft Technology, Inc.
December 1, 2009
Connect Timeout
0 to 65535
Defines the number of milliseconds to wait for the CD signal to be set high. The
CD signal indicates a connection is made using a dial-up modem.
First Character Delay
0 to 65535
Defines the number of milliseconds to wait before sending the first message after
the connection is first made. This delay only applies to the first packet sent to the
modem.
Redial Delay Time
0 to 32000
Defines the minimum number of milliseconds to wait before a redial attempt is
made by the slave.
Redial Random Delay
0 to 32000
Defines a random millisecond time range to be added to the redial delay time
before the modem is accessed.
Idle Timeout
0 to 65535
Defines the number of milliseconds the modem is inactive before it will
disconnect.
Phone Number
ASCII String Data
This field contains a null-terminated, ASCII character string used by the dial-up
modem. The string must contain all characters required by the modem. An
example string is ATDT1800222333. Maximum length is 34 bytes including the
terminating 0.
Collision Avoidance
Yes or No
This parameter defines if the collision avoidance functionality is to be applied to
the port. If the parameter is set to No, collision avoidance is not used. It will be
used if set to Yes. If collision avoidance is used, it requires a special cable.