Progres AMBITROL 100 Instruction Manual Download Page 20

 

 

20

TYPE 7 

Input of sensors, outlet by relay with modulation 

of the working time proportional to the changes of the 
sensors. 
 

The programme is given a reference, a 

proportional band and a maximum and minimum 
percentage of outlet. 
 

When the value of the sensor is lower than the 

reference, the outlet increases proportionally from the 
minimum to the maximum, obtaining this last one when 
the sensor reaches the value of reference minus the 
programmed proportional band. 
 

The value of time, called "cycle of modulation", 

corresponds to the 100% of the time of activation of 
outlet. If the value of proportion decreases, the outlet 
will be activated for as long as it corresponds from the 
percentage of the cycle of modulation and the rest of 
the proportion will not be activated. This will be 
repeated once the time of the cycle of modulation is 
finished. 
 
 

Example: proportional heating. 
 

CONSULT 

P03  HEAT-1  E  21.5 ºC 
S  025 % 

PROGRAMME 

P03  HEAT-1  C0 
Reference=  22.0 ºC 
Pro. Band=  02.0 ºC 
Min=  00%  Max=  090% 
High alarm(+)=  00.0 
Low alarm(-)=   03.8 
Manual (Yes/no)=  No 

 

CURVE1 

P03  HEAT-1  C1Pto1 
Pos=000 

Ref=34.0 ºC 

Pos=017 

Ref=26.5 ºC 

Pos=035 

Ref=23.5 ºC 

Pos=045 

Ref=22.0 ºC 

 
CURVE2 

P03  HEAT-1  C2Pto1 
Min=00% 

Max=090% 

Min=00% 

Max=085% 

Min=00% 

Max=075% 

Min=00% 

Max=070% 

 
CONFIGURATION 

P03  HEAT-1 
Type of working=  7 
Text= 02 

Number= 1 

Num. of inputs=  3 

Num. of outlet=  03 
Modulation cycle= 000 

Conditioning Pro.=  00 
Affects in code=  00 

 

RECORD 

HEAT-1   21/06  (047%) 
22.1 

21.2 

19.7  ºC 

 

High alarm 

 

 

20.0 

 

 

 

 

REFERENCE 

15.0 

 

 

 

Value of sensor 

 

 

 

 

 

10.0 

 

 

PROPORTIONAL BAND 

 

Low  

Alarm 

 

 

 

5.0 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum 

100%

 

 

 

 

 

 

 

 

 

 

Minimum 

0% 

 

 

 

 

 

   

 

 

 

 

   

 

 

 

 

State relay 

of outlet 

 

                                                      

 

Summary of Contents for AMBITROL 100

Page 1: ...atic premises such as farms greenhouses drying sheds cold rooms etc with 8 analogical inputs for sensors and 2 digital ones to condition working plus 8 analogical outlets of relay all nothing expandab...

Page 2: ...is work has to be done by an installator The USE is the chapter addressed to the user as it contains all the instructions about the programation and the follow up The equipment has and illuminated alp...

Page 3: ...ut of sensors outlet by relay When the value of the sensor is higher than the value of reference the outlet is activated until It reaches the value of the differential Examples Refrigeration drying et...

Page 4: ...modulation of the time of proportional activation to the changes of the sensors The programme is given a reference a proportional band and a maximum and minimum percentage of outlet When the value of...

Page 5: ...rth terminal bar with a section equal to the supply cables of the switchboard The equipment is protected in the supply by a varistor between the phase and t he neutral which will short circuit the fus...

Page 6: ...eened cable What is more this cable must never be installed by the power lines The screen of the cable will be connected to the earth terminal by one of its ends If there is not an earth terminal it w...

Page 7: ...12 0 Num of input 8 Tare 03 5 HR 76 3 To modify the value of the tare we have to calculate the error of the reading of the sensor and add or deduct it to the value of the tare Example Tare 03 5 HR 76...

Page 8: ...and outlets before as they are related to the programme First we can see the following screen asking for the number of PROGRAMME we want to access give the number and ENTER The equipment has capacity...

Page 9: ...the two existing digital inputs to connect securities external to the equipment if they are not used to count For the input 1 enter the code 81 and for the input 2 the code 82 in the blank for the con...

Page 10: ...differential of working This is done in the types of o utlet by relay types 1 2 6 except type 3 7 8 and 9 P02 VENT 1 C1pos 018 Differential 00 5 C This value is added or deducted according to the typ...

Page 11: ...and the second one will not stop until it has finished all the programme The programmes with analogical outlet or of proportional action are started when the outlet is over 60 and stop when it decreas...

Page 12: ...used by the programmes in order to do a variable and automatic control Here we can see a simple example P02 HEAT 1 C1 Point1 Pos 003 Ref 29 8 C Pos 008 Ref 27 5 C Pos 020 Ref 25 0 C Pos 045 Ref 20 0...

Page 13: ...ased The configuration the programmes and the curves are not erased Without battery E y n 27 03 Alarm in programme Any programme to which we have given values in high or low alarm and the value of the...

Page 14: ...changes in the timing programmes type 3 as no value of sensor is indicated but we indicate the value of time that is left to finish the working If it is in hours and minutes the format is 00 00 if it...

Page 15: ...S Stop PROGRAMME P06 HUMI 4 C0 Reference 75 0 HR Differential 03 0 HR High alarm 00 0 Low alarm 00 0 Manual Yes no No CURVE 1 P06 HUMI 4 C1Pto1 Pos 000 Ref 00 0 HR Pos 000 Ref 00 0 HR Pos 000 Ref 00...

Page 16: ...LUE OF SENSOR 20 0 REFERENCE DIFFERENTIAL 15 0 10 0 Low alarm 5 0 START STOP TYPE 3 Timing programme outlet by relay When the day and time programmed are reached the outlet is activated finishing when...

Page 17: ...ULT P03 HEAT 1 E 21 5 C S 025 PROGRAMME P03 HEAT 1 C0 Reference 22 0 C Pro Band 02 0 C Min 00 Max 090 High alarm 00 0 Low alarm 03 8 Manual Yes no No CURVE1 P03 HEAT 1 C1Pto1 Pos 000 Ref 34 0 C Pos 01...

Page 18: ...1 Num of inputs 1 4 Num of outlet 02 Conditioning Pro 00 Affects in code 00 RECORD VENT 1 21 06 083 24 9 23 4 22 4 C In the inputs of the powermeter of retromessage of window the maximum and minimum v...

Page 19: ...ifferential CONSULT P01 VTNA 0 E 24 8 C S Open PROGRAMME P01 VTNA 0 C0 Reference 24 0 C Differential 02 0 C Tim Open 05 s Pause Open 128 s Tim Close 100 s Pause Close 100s Manual Yes no No CURVE1 P01...

Page 20: ...the percentage of the cycle of modulation and the rest of the proportion will not be activated This will be repeated once the time of the cycle of modulation is finished Example proportional heating...

Page 21: ...e percentage of the cycle of modulation a nd the rest of the proportion will not be activated This will be repeated once the time of the cycle of modulation is finished Example proportional ventilatio...

Page 22: ...ensors CONSULT P05 VENT 1 E 25 1 C S 055 PROGRAMME P05 VENT 1 C0 Reference 24 0 C Pro Band 02 0 C Min 00 Max 100 High alarm 00 0 Low alarm 03 5 Manual Yes no No CURVE1 P05 VENT 1 C1Pto1 Pos 000 Ref 29...

Page 23: ...s distributed proportionally to the percentage required by every programme The types of working 7 and 8 can only use a sensor input the other types can do the average of two of them If the humidificat...

Page 24: ...24...

Reviews: