16
TYPE 2
Input of sensors, outlet by relay.
When the value of the sensor is higher than the
value of reference, the outlet is activated until it
reaches the value of the differential.
Examples: Refrigeration, drying, Maximum
alarm, etc.
CONSULT
P05 TERM-1 E 18.9 ºC
S Start
PROGRAMME
P05 TERM-1 C0
Reference= 20.0%ºC
Differential= 01.5%ºC
High alarm(+)= 04.0
Low alarm(-)= 06.0
Manual (Yes/no)= No
CURVE 1
P05 TERM-1 C1Pto1
Pos=000
Ref=24.0%ºC
Pos=012
Ref=22.0%ºC
Pos=020
Ref=21.3%ºC
Pos=032
Ref=19.5%ºC
CONFIGURATION
P05 TERM-1
Type of working= 2
Text= 01
Number= 1
Num. of inputs= 1
0
Num. of outlet= 07
Conditioning Pro.= 00
Affects in code= 00
RECORD
TERM-1 21/06 (03:32)
20.2
19.6
18.4 ºC
High alarm
VALUE OF SENSOR
20.0
REFERENCE
DIFFERENTIAL
15.0
10.0
Low alarm
5.0
START
STOP
TYPE 3
Timing programme, outlet by relay.
When the day and time programmed are
reached, the outlet is activated, finishing when there is
no more time of activation left. Up to 99 periodical
activations can be programmed, at the same time.
The programme can also be started obeying to
any other programme.
Example: Lighting, feeding, irrigation,
humidification by time, when the humidity of a certain
value decreases.
CONSULT
P04 WATER-1 E 00:12
S Start
PROGRAMME
P04 WATER-1 C0
Start= 08:00
Days= SMTWTFS
T.working= 00:15
N. workings= 02
Frequency= 06:00
Manual (Yes/No)= No
CURVE1
P04 WATER-1 C1Pto1
Pos=000
Ref=00:11
Pos=025
Ref=00:14
Pos=045
Ref=00:19
Pos=130
Ref=00:28
CONFIGURATION
P04 WATER-1
Type of working= 3
Text= 01
Number= 1
Num. of outlet= 03
(h:m):0
(m.s):1
00
Conditioning Pro= 00
RECORD
WATER-1 27/06 (00:30)
Summary of Contents for AMBITROL 100
Page 24: ...24...