10
6. USE
6.1. PROGRAMMES
To acced to every one of the programmes of
values (not of Configuration) press the key "FUN" and
choose option 1, then it will ask the number of
programme.
F1:
Programmes
F2:
Curves
Num. of programme= 00
(for values)
Once we have entered the number, it shows the
following screen, in which for two seconds, it informs
about the type of working of the programme.
P03 HEAT-1 C0
Type of working= 1
Once the timing is finished, in the second line,
the message of type of working is normally replaced by
the value of the reference.
P03 HEAT-1 C0
Reference= 22.0 ºC
The cursor is placed in the value of the curve
"C". If the value is zero "C0", the datum of the
reference will be entered manually.
If you want that the value of reference changes
automatically as time goes by, we will have to activate
the curve that every programme has, giving the value
"1".
If you do not want to modify the number of
curve, press the key "ENTER" and then it will ask the
value of reference.
P02 VENT-1 C1pos=018
Reference= 22.6 ºC
Once the curve is activated, it will ask the
position (pos) in the curve, which goes from 0 to 250
days.
The position increases automatically every day
at 0 hours and can be modified at any moment.
The value of reference is updated automatically
every hour.
With the cursor placed in "pos", we can modify
the value or press directly "ENTER", placing the cursor
at the right side of the lower line.From this point,
pressing the key with the arrow we can modify again
"pos".
When the curve is activated, the value of
reference can not be modified directly.
Once the value of reference has been entered, it
asks for the "differential" of working; This is done in the
types of outlet by relay (types 1-2-6, except type 3,7,8
and 9).
P02 VENT-1 C1pos=018
Differential= 00.5 ºC
This value is added or deducted, according to
the type of working, to the reference to calculate the
stop of the working.
In the types with analogical outlet (types 4-5), of
proportional action (types 7-8) and proportional
window (type 9), we are asked for the "proportional
band", which is also added or deducted to the
reference so that the value of outlet reaches the
maximum of its value.
For these types, it will later ask for the maximum
and minimum value of outlet. This is useful to maintain
tops in the value of outlet even though the value of the
sensor is moved from the referenced values.
If the curve is active, we will not be able to
change directly the maximum and minimum values.
Every programme, except the types 3-6 (timing,
window), will be asked some values of high and low
alarm.
P03 HEAT-1 C0
High alarm(+)= 03.0
P03 HEAT-1 C0
Low alarm(-)= 02.5
These values are added (high) and deducted
(low) to the reference and, if the value of the sensor is
superior to the added value or is inferior to the
deducted value and it stays like that for at least 30
seconds, the relay of alarm (outlet 8) will be activated
until this condition disappears.
The programme, date and time when this
happened will also be registered in the section of
ANOMALIES.
If the values of alarm are entered in negative,
the alarm will be activated as long as the value of the
sensor is between the two values of alarm.
At the end of every programme, it asks if we
want to act on the outlet manually.
P03 HEAT-1 C0
Manual (Yes/No)= No
If we answer with the key "SI" (YES) and
"ENTER", different screens will appear depending on
the type of working:
FOR TYPE 1 AND 2 (outlet by relay)
P03 HEAT-1 C0
Start:1
Stop:0 = 0