Progres AMBITROL 100 Instruction Manual Download Page 11

 

11

 

A "1" starts the outlet and a "0" deactivates it, 

this happens indefinitely in all the types, as long as we 
do not answer "NO" to the question of Manual 
(Yes/No). 
 
FOR TYPE 3 (timing relay) 
 

P03  WATER 

C0 

Start:1 

Stop:0  =  0 

 

FOR TYPES 4-5 (analogical) AND 7-8-9 (proportional) 
We enter the value that we want in the outlet. 
 

P03  HEAT-1 C0 
Outlet= 089% 

 

FOR TYPE 6 (windows) 

 

P03  VTNA-1 C0 
Stop:0  Op.:1  Cl.:2=0 

0:Stop 

1:Open 

2:Close 

 

6.1.1. TIMING PROGRAMMES (TYPE 3) 

In the timing programmes, type 3, we will be ask 

some different questions about the values of the 
programme:  
 

P03  HEAT-1 C0 
Start=08:00 

 

P03  HEAT-1 C0 
Days=SMTWTFS 

 

P03  HEAT-1 C1pos=015 
T. working= 00:00 

 

P03 

C0 

N. workings= 00 

 

The "start" is the time when the programme will 

start working in relation to the question of "days". 
 

To programme the days, press the keys that 

have the days on them, pressing once to programme it 
and once to erase it. To enter or erase all the days 
press the key "daily". 

A variant in the "start" of the programme is that 

instead of start working by timing it can do so by 
command of another programme, to do so in the value 
of the time of start, we will enter the code 90 or 91 and, 
in the minutes, the number of programme that will start 
this one.  
 

The difference between code 90 and 91 is that 

the first one will stop if the programme which started it 
goes from start to stop and the second one will not 
stop until it has finished all the programme. 

 

The programmes with analogical outlet or of 

proportional action are started when the outlet is over 
60% and stop when it decreases below 40% 
 

Then it asks if it will work with curve. If we 

answer yes, it also asks for the position. 
 

The next question is "Time of working", which is 

the time that the outlet will be working. 
 

The "Number of workings" is the number of 

times that it will repeat the working. 
 

The "Frequency" is the time between the starts 

of different workings. 
 
 

Both the "Time of working" and the "Frequency" 

can work in hours and minutes or in minutes and 
seconds. (This selection will be done in Configuration).  
 

If the programme is started  manually, the outlet 

will start during the programmed time and the cycles, 
cancelling automatically the MANUAL state in order  to 
be activated automatically. 
 

If there is an electric cut during the time of start, 

when the power is back the programme will already be 
started. 
 

If the programme is started and it has not 

finished the previous working completely, the number 
of workings will be added. 
 

To cancel the time left when the programme is 

working, start the MANUAL at Stop and then take out 
the Manual answering "NO". 

6.1.2. WINDOWS (TYPE 6) 

Another variant in the questions is, for the type 6 

that works on windows: 
 

P01  VTNA-1 C0 
Reference=  24.0  ºC 

 

P01  VTNA-1 C0 
Differential=  05.0  ºC 
P01  VTNA-1 C0 
Timing open = 05 s 

 

P01  VTNA-1 C0 
Pause open = 128 s 

 

P01  VTNA-1 C0 
Timing close= 08 s 

 
 

P01  VTNA-1 C0 
Pause close= 128 s 

 

P01  VTNA-1 C0 

Summary of Contents for AMBITROL 100

Page 1: ...atic premises such as farms greenhouses drying sheds cold rooms etc with 8 analogical inputs for sensors and 2 digital ones to condition working plus 8 analogical outlets of relay all nothing expandab...

Page 2: ...is work has to be done by an installator The USE is the chapter addressed to the user as it contains all the instructions about the programation and the follow up The equipment has and illuminated alp...

Page 3: ...ut of sensors outlet by relay When the value of the sensor is higher than the value of reference the outlet is activated until It reaches the value of the differential Examples Refrigeration drying et...

Page 4: ...modulation of the time of proportional activation to the changes of the sensors The programme is given a reference a proportional band and a maximum and minimum percentage of outlet When the value of...

Page 5: ...rth terminal bar with a section equal to the supply cables of the switchboard The equipment is protected in the supply by a varistor between the phase and t he neutral which will short circuit the fus...

Page 6: ...eened cable What is more this cable must never be installed by the power lines The screen of the cable will be connected to the earth terminal by one of its ends If there is not an earth terminal it w...

Page 7: ...12 0 Num of input 8 Tare 03 5 HR 76 3 To modify the value of the tare we have to calculate the error of the reading of the sensor and add or deduct it to the value of the tare Example Tare 03 5 HR 76...

Page 8: ...and outlets before as they are related to the programme First we can see the following screen asking for the number of PROGRAMME we want to access give the number and ENTER The equipment has capacity...

Page 9: ...the two existing digital inputs to connect securities external to the equipment if they are not used to count For the input 1 enter the code 81 and for the input 2 the code 82 in the blank for the con...

Page 10: ...differential of working This is done in the types of o utlet by relay types 1 2 6 except type 3 7 8 and 9 P02 VENT 1 C1pos 018 Differential 00 5 C This value is added or deducted according to the typ...

Page 11: ...and the second one will not stop until it has finished all the programme The programmes with analogical outlet or of proportional action are started when the outlet is over 60 and stop when it decreas...

Page 12: ...used by the programmes in order to do a variable and automatic control Here we can see a simple example P02 HEAT 1 C1 Point1 Pos 003 Ref 29 8 C Pos 008 Ref 27 5 C Pos 020 Ref 25 0 C Pos 045 Ref 20 0...

Page 13: ...ased The configuration the programmes and the curves are not erased Without battery E y n 27 03 Alarm in programme Any programme to which we have given values in high or low alarm and the value of the...

Page 14: ...changes in the timing programmes type 3 as no value of sensor is indicated but we indicate the value of time that is left to finish the working If it is in hours and minutes the format is 00 00 if it...

Page 15: ...S Stop PROGRAMME P06 HUMI 4 C0 Reference 75 0 HR Differential 03 0 HR High alarm 00 0 Low alarm 00 0 Manual Yes no No CURVE 1 P06 HUMI 4 C1Pto1 Pos 000 Ref 00 0 HR Pos 000 Ref 00 0 HR Pos 000 Ref 00...

Page 16: ...LUE OF SENSOR 20 0 REFERENCE DIFFERENTIAL 15 0 10 0 Low alarm 5 0 START STOP TYPE 3 Timing programme outlet by relay When the day and time programmed are reached the outlet is activated finishing when...

Page 17: ...ULT P03 HEAT 1 E 21 5 C S 025 PROGRAMME P03 HEAT 1 C0 Reference 22 0 C Pro Band 02 0 C Min 00 Max 090 High alarm 00 0 Low alarm 03 8 Manual Yes no No CURVE1 P03 HEAT 1 C1Pto1 Pos 000 Ref 34 0 C Pos 01...

Page 18: ...1 Num of inputs 1 4 Num of outlet 02 Conditioning Pro 00 Affects in code 00 RECORD VENT 1 21 06 083 24 9 23 4 22 4 C In the inputs of the powermeter of retromessage of window the maximum and minimum v...

Page 19: ...ifferential CONSULT P01 VTNA 0 E 24 8 C S Open PROGRAMME P01 VTNA 0 C0 Reference 24 0 C Differential 02 0 C Tim Open 05 s Pause Open 128 s Tim Close 100 s Pause Close 100s Manual Yes no No CURVE1 P01...

Page 20: ...the percentage of the cycle of modulation and the rest of the proportion will not be activated This will be repeated once the time of the cycle of modulation is finished Example proportional heating...

Page 21: ...e percentage of the cycle of modulation a nd the rest of the proportion will not be activated This will be repeated once the time of the cycle of modulation is finished Example proportional ventilatio...

Page 22: ...ensors CONSULT P05 VENT 1 E 25 1 C S 055 PROGRAMME P05 VENT 1 C0 Reference 24 0 C Pro Band 02 0 C Min 00 Max 100 High alarm 00 0 Low alarm 03 5 Manual Yes no No CURVE1 P05 VENT 1 C1Pto1 Pos 000 Ref 29...

Page 23: ...s distributed proportionally to the percentage required by every programme The types of working 7 and 8 can only use a sensor input the other types can do the average of two of them If the humidificat...

Page 24: ...24...

Reviews: