A "1" starts the outlet and a "0" deactivates it,
this happens indefinitely in all the types, as long as we
do not answer "NO" to the question of Manual
(Yes/No).
FOR TYPE 3 (timing relay)
P03 WATER
C0
Start:1
Stop:0 = 0
FOR TYPES 4-5 (analogical) AND 7-8-9 (proportional)
We enter the value that we want in the outlet.
P03 HEAT-1 C0
Outlet= 089%
FOR TYPE 6 (windows)
P03 VTNA-1 C0
Stop:0 Op.:1 Cl.:2=0
0:Stop
1:Open
2:Close
6.1.1. TIMING PROGRAMMES (TYPE 3)
In the timing programmes, type 3, we will be ask
some different questions about the values of the
programme:
P03 HEAT-1 C0
Start=08:00
P03 HEAT-1 C0
Days=SMTWTFS
P03 HEAT-1 C1pos=015
T. working= 00:00
P03
C0
N. workings= 00
The "start" is the time when the programme will
start working in relation to the question of "days".
To programme the days, press the keys that
have the days on them, pressing once to programme it
and once to erase it. To enter or erase all the days
press the key "daily".
A variant in the "start" of the programme is that
instead of start working by timing it can do so by
command of another programme, to do so in the value
of the time of start, we will enter the code 90 or 91 and,
in the minutes, the number of programme that will start
this one.
The difference between code 90 and 91 is that
the first one will stop if the programme which started it
goes from start to stop and the second one will not
stop until it has finished all the programme.
The programmes with analogical outlet or of
proportional action are started when the outlet is over
60% and stop when it decreases below 40%
Then it asks if it will work with curve. If we
answer yes, it also asks for the position.
The next question is "Time of working", which is
the time that the outlet will be working.
The "Number of workings" is the number of
times that it will repeat the working.
The "Frequency" is the time between the starts
of different workings.
Both the "Time of working" and the "Frequency"
can work in hours and minutes or in minutes and
seconds. (This selection will be done in Configuration).
If the programme is started manually, the outlet
will start during the programmed time and the cycles,
cancelling automatically the MANUAL state in order to
be activated automatically.
If there is an electric cut during the time of start,
when the power is back the programme will already be
started.
If the programme is started and it has not
finished the previous working completely, the number
of workings will be added.
To cancel the time left when the programme is
working, start the MANUAL at Stop and then take out
the Manual answering "NO".
6.1.2. WINDOWS (TYPE 6)
Another variant in the questions is, for the type 6
that works on windows:
P01 VTNA-1 C0
Reference= 24.0 ºC
P01 VTNA-1 C0
Differential= 05.0 ºC
P01 VTNA-1 C0
Timing open = 05 s
P01 VTNA-1 C0
Pause open = 128 s
P01 VTNA-1 C0
Timing close= 08 s
P01 VTNA-1 C0
Pause close= 128 s
P01 VTNA-1 C0